Trane BCI-I Integration Manual page 38

Bacnet communication interface for intellipak and commercial self-contained
Table of Contents

Advertisement

Table 11. All Object Types Sorted by Object Name (
(a)
Object Identifier
Object Name
Binary Output, 16
Humidification Command
NC 3
HVAC-Advisory
NC 1
HVAC-Critical
NC 4
HVAC-Information
NC 2
HVAC-Service Required
Analog Input, 25
Mixed Air Temperature
Analog Input, 54
Morning Warmup Air Temperature Setpoint Active
Analog Output, 4
Morning Warmup Setpoint BAS
Multi-State Output, 7
Occupancy Mode Request BAS
Multi-State Input, 20
Occupancy Mode Status
Analog Output, 29
Occupied Temperature Offset BAS
Analog Input, 11
Outdoor Air Damper Position Status
Multi-State Input, 43
Outdoor Air Damper Status
Analog Input, 22
Outdoor Air Dewpoint
Analog Input, 23
Outdoor Air Enthalpy
Analog Input, 34
Outdoor Air Flow Active
Analog Output, 17
Outdoor Air Flow BAS
Analog Input, 20
Outdoor Air Humidity Active
Analog Output, 15
Outdoor Air Humidity BAS
Analog Input, 21
Outdoor Air Humidity Local
Analog Input, 57
Outdoor Air Minimum Flow Setpoint Active
Analog Output, 16
Outdoor Air Minimum Flow Setpoint BAS
Analog Input, 18
Outdoor Air Temperature Active
Analog Output, 14
Outdoor Air Temperature BAS
Analog Input, 19
Outdoor Air Temperature Local
Multi-State Input, 34
Prefilter Status
Analog Input, 82
Preheat Type
Multi-State Input, 35
Primary Filter Status
Analog Input, 5
Reheat Capacity Status
Analog Input, 83
Reheat Type
Analog Input, 26
Return Air Temperature
Analog Input, 30
Return Fan Air Pressure
Multi-State Input, 40
Return Fan Proving Status
Analog Input, 10
Return Fan Speed Command
Multi-State Input, 42
Return Fan Status
Binary Input, 11
Service Test Mode Status
Analog Output, 11
Space Air Temperature BAS
Analog Input, 87
Space Air Temperature Local
Analog Input, 50
Space Air Temperature Setpoint Active
Analog Output, 2
Space Air Temperature Setpoint BAS
Analog Input, 32
Space CO
Analog Output, 18
Space CO
Analog Input, 84
Space CO2 High Limit Setpoint
Analog Input, 85
Space CO2 Low Limit Setpoint
Analog Output, 21
Space Dehumidification Setpoint BAS
Analog Input, 17
Space Enthalpy
ACC-SVP01B-EN • BCI-I Integration Guide
Refer to previous tables for detailed descriptions of objects
Concentration Active
2
Concentration BAS
2
Object Data Points and Diagnostic Data Points
Description
Command the operating state of the humidification system.
HVAC-Advisory
HVAC-Critical
HVAC-Information
HVAC-Service Required
The mixed air temperature value from a unit-mounted sensor.
The air temperature setpoint used during morning warmup mode.
BAS supplied temperature setpoint used in morning warmup mode.
Command the unit into an occupancy mode.
Indicates the current occupancy mode of the unit.
Offset used to calculate setpoints in occupied mode.
Indicates the unit outdoor air damper position.
Indicates the operating state of the outdoor damper.
The outdoor air dewpoint value being utilized by the unit.
The outdoor air enthalpy value being utilized by the unit.
Outdoor airflow utilized by the unit.
BAS supplied outdoor airflow sensor value.
The outdoor air humidity value used for unit control.
BAS supplied outdoor air humidity sensor value.
The outdoor air humidity value from a unit-mounted sensor.
The minimum outdoor airflow setpoint being utilized by the unit.
BAS supplied minimum outdoor airflow setpoint.
The outdoor air temperature currently used for unit control.
BAS supplied outdoor air temperature sensor value.
The outdoor air temperature value from a unit-mounted sensor.
Indicates the prefilter media state.
Describes the heating type installed in the unit.
Indicates the primary filter media state.
Indicates the unit reheat heating capacity being utilized.
Describes the reheat type installed in the unit.
The return air temperature value from a unit-mounted sensor.
Return fan air pressure value measured by a unit-mounted sensor.
Indicates the current state of the return fan.
Indicates the unit commanded return fan speed.
Indicates the state of the return fan.
Indicates if the unit is in service test mode.
BAS supplied space air temperature sensor value.
The space air temperature measured by a unit-mounted sensor.
Space temperature setpoint value being used for unit control.
Base value to calculate setpoints in occupied and standby modes.
Space CO
concentration being used for unit control.
2
BAS supplied space CO
sensor value.
2
Indicates the high limit space CO
2
Indicates the low limit space CO
setpoint for ventilation.
2
BAS supplied space dehumidification setpoint value.
The space enthalpy value from a unit-mounted control.
) (continued)
setpoint for ventilation.
37