Trane BCI-I Integration Manual page 26

Bacnet communication interface for intellipak and commercial self-contained
Table of Contents

Advertisement

Table 3.
Analog Output (continued)
Object Identifier Object Name
Analog Output, 25
Space Humidity BAS
Analog Output, 26
Space Humidification Setpoint BAS
Analog Output, 29
Occupied Temperature Offset BAS
Analog Output, 30
Standby Temperature Offset BAS
Unoccupied Cooling Temperature Setpoint
Analog Output, 31
BAS
Unoccupied Heating Temperature Setpoint
Analog Output, 32
BAS
Table 4.
Analog Input
Object Identifier
Analog Input, 1
Cooling Capacity Status
Analog Input, 2
Heat Primary Capacity Status
Analog Input, 3
Heat Secondary Capacity Status
Analog Input, 5
Reheat Capacity Status
Analog Input, 6
Filter Runtime Hours
Analog Input, 7
Supply Fan Speed Command
Analog Input, 8
Exhaust Fan Speed Command
Analog Input, 9
Exhaust Damper Position Status
Analog Input, 10
Return Fan Speed Command
Analog Input, 11
Outdoor Air Damper Position Status
Analog Input, 12
Waterside Economizer Valve Position Status
Analog Input, 13
Frost Avoidance Temperature Setpoint
Analog Input, 14
Condenser Capacity Status
Analog Input, 15
Space Temperature Active
Analog Input, 16
Space Humidity Active
Analog Input, 17
Space Enthalpy
Analog Input, 18
Outdoor Air Temperature Active
Analog Input, 19
Outdoor Air Temperature Local
Analog Input, 20
Outdoor Air Humidity Active
Analog Input, 21
Outdoor Air Humidity Local
Analog Input, 22
Outdoor Air Dewpoint
Analog Input, 23
Outdoor Air Enthalpy
Analog Input, 24
Discharge Air Temperature Active
Analog Input, 25
Mixed Air Temperature
Analog Input, 26
Return Air Temperature
ACC-SVP01B-EN • BCI-I Integration Guide
Description
BAS supplied space humidity
sensor value.
BAS supplied space
humidification setpoint value.
Offset used to calculate setpoints
in occupied mode.
Offset value used to calculate
setpoints in standby mode.
Cooling temperature setpoint
used for control in unoccupied
mode.
Heating temperature setpoint
used for control in unoccupied
mode.
Object Name
Indicates the unit cooling capacity being utilized.
Indicates the unit primary heating capacity being
utilized.
Indicates the unit secondary heating capacity being
utilized.
Indicates the unit reheat heating capacity being
utilized.
Indicates the number of hours air has flowed through
the filter.
Indicates the unit commanded supply fan speed.
Indicates the unit commanded exhaust fan speed.
Indicates the unit exhaust damper position.
Indicates the unit commanded return fan speed.
Indicates the unit outdoor air damper position.
Indicates the unit waterside economizer valve position.
Indicates the frost coil avoidance temperature setpoint.
Indicates the unit condenser capacity being utilized.
The space temperature currently used for unit control.
The space humidity value from a unit-mounted control.
The space enthalpy value from a unit-mounted control.
The outdoor air temperature currently used for unit
control.
The outdoor air temperature value from a unit-
mounted sensor.
The outdoor air humidity value used for unit control.
The outdoor air humidity value from a unit-mounted
sensor.
The outdoor air dewpoint value being utilized by the
unit.
The outdoor air enthalpy value being utilized by the
unit.
The discharge air temperature currently used for unit
control.
The mixed air temperature value from a unit-mounted
sensor.
The return air temperature value from a unit-mounted
sensor.
Object Data Points and Diagnostic Data Points
Units
Percent (98)
Percent (98)
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64)
Description
Refresh
Rate
Valid Range
(Sec.)
10 to 90
900
20 to 50
NA
1.0 to 5.0
NA
1.0 to 10.0
NA
52.0 to 88.0
NA
50.0 to 90.0
NA
Units (Listed Are Defaults)
Percent (98)
Percent (98)
Percent (98)
Percent (98)
Hours (71)
Percent (98)
Percent (98)
Percent (98)
Percent (98)
Percent (98)
Percent (98)
Degrees-Fahrenheit (64)
Percent (98)
Degrees-Fahrenheit (64)
Percent-relative-humidity (29)
BTUs-per-pound (117)
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64)
Percent-relative-humidity (29)
Percent-relative-humidity (29)
Degrees-Fahrenheit (64
BTUs-per-pound (117)
Degrees-Fahrenheit (64)
Degrees-Fahrenheit (64
Degrees-Fahrenheit (64
25