Object Data Points and Diagnostic Data Points
Table 11. All Object Types Sorted by Object Name (
(a)
Object Identifier
Object Name
Multi-State Input, 44
Economizer System Status
Multi-State Input, 9
Economizer Type
Multi-State Output, 3
Economizer Waterside Enable BAS
Analog Input, 70
Economizing Enthalpy Enable Setpoint
Analog Input, 69
Economizing Temperature Enable Setpoint
Multi-State Output, 2
Emergency Override BAS
Analog Input, 64
Energy Recovery Exhaust Air Bypass Damper Position
Binary Input, 26
Energy Recovery Frost Avoidance Status
Analog Input, 65
Energy Recovery Leaving Exhaust Air Temperature
Analog Input, 66
Energy Recovery Outdoor Air Bypass Damper Position
Binary Input, 28
Energy Recovery Preheat Status
Binary Input, 27
Energy Recovery Status
Analog Input, 36
Evaporator Entering Temperature Circuit 1
Analog Input, 37
Evaporator Entering Temperature Circuit 2
Binary Input, 161
Evaporator Frost Protection Circuit 1 Status
Binary Input, 162
Evaporator Frost Protection Circuit 2 Status
Binary Input, 163
Evaporator Frost Protection Circuit 3 Status
Binary Input, 164
Evaporator Frost Protection Circuit 4 Status
Analog Input, 38
Evaporator Leaving Temperature Circuit 1
Analog Input, 39
Evaporator Leaving Temperature Circuit 2
Analog Input, 40
Evaporator Leaving Temperature Circuit 3
Analog Input, 41
Evaporator Leaving Temperature Circuit 4
Analog Input, 9
Exhaust Damper Position Status
Analog Input, 71
Exhaust Enable Damper Position Setpoint
Multi-State Input, 39
Exhaust Fan Proving Status
Analog Input, 8
Exhaust Fan Speed Command
Multi-State Input, 38
Exhaust Fan Status
Analog Input, 90
Exhaust or Return Fan Type
Analog Input, 6
Filter Runtime Hours
Analog Value, 1
Filter Runtime Hours Setpoint
Binary Output, 13
Filter Timer Reset Command
Multi-State Input, 36
Final Filter Status
Analog Input, 13
Frost Avoidance Temperature Setpoint
Analog Output, 20
Heat Capacity Enable Setpoint BAS
Binary Output, 5
Heat Lockout Command
Binary Output, 12
Heat or Reheat Enable Command
Multi-State Input, 29
Heat Output 1
Multi-State Input, 30
Heat Output 2
Multi-State Input, 31
Heat Output 3
Multi-State Input, 32
Heat Output 4
Multi-State Input, 33
Heat Output 5
Analog Input, 2
Heat Primary Capacity Status
Analog Input, 3
Heat Secondary Capacity Status
Multi-State Input, 18
Heating Reset Type Status
Multi-State Input, 23
Heating Setpoint Source
Analog Input, 76
Humidification Capacity Status
36
Refer to previous tables for detailed descriptions of objects
Description
Indicates the operating state of the waterside economizer system.
General description of the equipment economizer system.
Command the state of the waterside economizer system.
Enthalpy setpoint below which economizing can be used.
Temperature setpoint below which economizing can be used.
Command the unit into an emergency mode of operation.
Energy recovery exhaust air bypass damper position.
Status of the energy recovery system frost protection function.
Energy recovery leaving exhaust air temperature.
Energy recovery outdoor air bypass damper position.
Indicates the status of the energy recovery preheat function.
Indicates the status of the energy recover system.
Indicates the entering evaporator temperature for circuit 1.
Indicates the entering evaporator temperature for circuit 2.
The status of evaporator frost protection function for circuit 1.
The status of evaporator frost protection function for circuit 2.
The status of evaporator frost protection function for circuit 3.
The status of evaporator frost protection function for circuit 4.
Indicates the leaving evaporator temperature for circuit 1
Indicates the leaving evaporator temperature for circuit 2.
Indicates the leaving evaporator temperature for circuit 3.
Indicates the leaving evaporator temperature for circuit 4.
Indicates the unit exhaust damper position.
Exhaust air damper minimum position to enable exhaust sequence.
Indicates if the unit exhaust fan is off or on.
Indicates the unit commanded exhaust fan speed.
Indicates the commanded state of the exhaust fan.
Describes the exhaust or return fan type installed in the unit.
Indicates the number of hours air has flowed through the filter.
The setpoint value used by the filter run hours calculation.
Command the unit to reset the accumulated filter run hours.
Indicates the final filter media state.
Indicates the frost coil avoidance temperature setpoint.
BAS supplied heating demand limit capacity setpoint value.
Command the unit to prevent heating operation.
Enable the heating or reheating system during dehumidification mode.
Indicates the commanded state of heating output 1.
Indicates the commanded state of heating output 2.
Indicates the commanded state of heating output 3.
Indicates the commanded state of heating output 4.
Indicates the commanded state of heating output 5.
Indicates the unit primary heating capacity being utilized.
Indicates the unit secondary heating capacity being utilized.
Indicates the type of heating reset.
Indicates the source of the space heating setpoint.
Indicates the unit humidification capacity being utilized.
) (continued)
ACC-SVP01B-EN • BCI-I Integration Guide