Trane BCI-I Integration Manual page 36

Bacnet communication interface for intellipak and commercial self-contained
Table of Contents

Advertisement

Table 11. All Object Types Sorted by Object Name (
(a)
Object Identifier
Object Name
Analog Input, 43
Condensing Saturated Temperature Circuit 2
Analog Input, 44
Condensing Saturated Temperature Circuit 3
Analog Input, 45
Condensing Saturated Temperature Circuit 4
Analog Output, 19
Cool Capacity Enable Setpoint BAS
Binary Output, 6
Cool Lockout Command
Multi-State Input, 25
Cool Output 1
Multi-State Input, 26
Cool Output 2
Multi-State Input, 27
Cool Output 3
Multi-State Input, 28
Cool Output 4
Analog Input, 81
Cool Type
Analog Input, 1
Cooling Capacity Status
Multi-State Input, 17
Cooling Reset Type Status
Multi-State Input, 22
Cooling Setpoint Source
Daytime Warmup Air Temperature Initiate Setpoint
Analog Input, 55
Active
Analog Input, 67
Daytime Warmup Initiate Temperature Setpoint Local
Analog Input, 68
Daytime Warmup Terminate Temperature Setpoint
Analog Output, 5
Daytime Warmup Terminate Temperature Setpoint BAS BAS supplied daytime warmup terminate temperature setpoint.
Analog Input, 79
Dehumidification Capacity Status
Binary Output, 15
Dehumidification Command
Analog Input, 58
Dehumidification High Limit Setpoint
Binary Input, 10
Demand Limit Status
Binary Output, 14
Diagnostic Reset Command
Binary Input, 166
Diagnostic Stop Status
Analog Output, 6
Discharge Air Cooling Setpoint BAS
Analog Output, 22
Discharge Air Dewpoint Setpoint BAS
Analog Input, 60
Discharge Air Dewpoint Temperature Setpoint
Analog Output, 7
Discharge Air Heating Setpoint BAS
Analog Input, 61
Discharge Air Reheat Setpoint Active
Analog Output, 23
Discharge Air Reheat Setpoint BAS
Analog Input, 24
Discharge Air Temperature Active
Analog Output, 12
Discharge Air Temperature BAS
Analog Input, 33
Discharge Air Temperature Dewpoint
Analog Input, 52
Discharge Air Temperature Setpoint Active
Analog Input, 28
Duct Static Air Pressure Active
Analog Output, 13
Duct Static Air Pressure BAS
Analog Input, 29
Duct Static Air Pressure Local
Analog Input, 48
Duct Static Air Pressure Setpoint Active
Analog Output, 8
Duct Static Air Pressure Setpoint BAS
Multi-State Output, 1
Economizer Airside Enable BAS
Multi-State Output, 1
Economizer Airside Enable BAS
Binary Input, 22
Economizer Airside Enable Status
Multi-State Input, 15
Economizer Decision Method
Binary Output, 7
Economizer Minimum Position Command
Analog Input, 56
Economizer Minimum Position Setpoint Active
Analog Output, 1
Economizer Minimum Position Setpoint BAS
Analog Input, 86
Economizer Minimum Position Setpoint Local
ACC-SVP01B-EN • BCI-I Integration Guide
Object Data Points and Diagnostic Data Points
Refer to previous tables for detailed descriptions of objects
Description
Indicates the saturated condenser temperature for circuit 2.
Indicates the saturated condenser temperature for circuit 3.
Indicates the saturated condenser temperature for circuit 4.
BAS supplied cooling demand limit capacity setpoint value.
Command the unit to prevent cooling operation.
Indicates the commanded state of cooling output 1.
Indicates the commanded state of cooling output 2.
Indicates the commanded state of cooling output 3.
Indicates the commanded state of cooling output 4.
Describes the cooling type installed in the unit.
Indicates the unit cooling capacity being utilized.
Indicates the type of cooling reset.
Indicates the source of the space cooling setpoint.
The air temperature setpoint used to start daytime warmup mode.
The local daytime warmup initiate temperature setpoint.
Temperature setpoint that will exit daytime warmup mode.
Indicates the unit dehumidification capacity being utilized.
Command the operating state of the dehumidification system.
Humidity setpoint value that starts dehumidification control.
Indicates if the unit is in an energy-demand limit mode
Command the unit to reset and clear diagnostics.
Indicates if the unit diagnostic has caused the unit to shutdown.
BAS supplied discharge air temperature cooling setpoint value.
BAS supplied discharge air dewpoint setpoint value.
Humidity setpoint value used during dehumidification control.
BAS supplied discharge air temperature heating setpoint value.
Indicates the active supply air reheat temperature setpoint.
BAS supplied discharge air reheat setpoint value.
The discharge air temperature currently used for unit control.
BAS supplied discharge air temperature sensor value.
Discharge air temperature dewpoint being used by the unit.
Discharge air temperature setpoint value being used for unit control.
Duct static air pressure value currently being used for unit control.
BAS supplied duct static air pressure sensor value.
Duct static air pressure value measured by a unit-mounted sensor.
Duct static pressure setpoint value being used for unit control.
BAS supplied duct static air pressure setpoint value.
Command the state of the airside economizer system.
Command the state of the airside economizer system.
Indicates the status of the airside economizer system.
Unit method to determine when the economizer system is enabled.
Command the unit to economizer minimum position operation.
The minimum position value the economizer damper will utilize.
BAS supplied economizer position minimum setpoint value.
Indicates the local economizer minimum position setpoint.
) (continued)
35