Object Data Points and Diagnostic Data Points
Table 6.
Multistate Output
BCI-I Object Identifier
Multi-State Output, 1
Multi-State Output, 2
Multi-State Output, 3
Multi-State Output, 7
Multi-State Output, 8
Multi-State Output, 10
Table 7.
Multistate Input
BCI-I Object
Identifier
Object Name
Multi-State Input, 2
Trane Unit Type
Multi-State Input, 9
Economizer Type
Multi-State Input, 10
Condenser Type
Multi-State Input, 13
Ventilation Override Status
28
Object Name
Economizer Airside Enable BAS
Emergency Override BAS
Economizer Waterside Enable BAS
Occupancy Mode Request BAS
Application Mode Request BAS
Condenser Water Flow BAS
Description
General description of the equipment-type
classification.
General description of the equipment
economizer system.
General description of the equipment
condenser system.
Indicates if the unit is in a ventilation
override mode of operation.
Description
Command the state of the airside economizer system.
Command the unit into an emergency mode of operation.
Command the state of the waterside economizer system.
Command the unit into an occupancy mode.
Command the unit to a specific application mode.
Command the unit to utilize a remote water flow
indication.
Object States
1 = 1 Heat/1 Cool
2 = Heat Pump
3 = Blower Coil
4 = Unit Ventilator
5 = Fan Coil
6 = Rooftop
7 = Air Handler
8 = Vertical Self Contained
9 = Unitary
10 = VAV Box
11 = Fan Coil
1 = None
2 = 2 Position Ventilation
3 = Modulation Economizer
4 = 2 Position Ventilation/Waterside Economizer
5 = Waterside Economizer
6 = Airside/Waterside Economizer
7 = TRAQ Damper
8 = Airside Economizer and TRAQ Damper/Sensor
9 = Waterside Economizer and TRAQ Damper/Sensor
10 = Airside/Waterside Economizer and TRAQ Damper/Sensor
1 = None
2 = Air Cooled
3 = Water Cooled
4 = Evaporative
1= Inactive
2= Mode A Active
3= Mode B Active
4= Mode C Active
5= Mode D Active
6= Mode E Active
ACC-SVP01B-EN • BCI-I Integration Guide
Object States
1 = Disabled
2 = Enabled
3 = Auto
1 = Normal
2 = Pressurize
3 = Depressurize
4 = Purge
5 = Shutdown
6 = Fire
1 = Disabled
2 = Enabled
3 = Auto
1 = Occupied
2= Unoccupied
3 = Occupied Bypass
4 = Occupied Standby
1 = Auto
2 = Heat
3 = Morning Warmup
4 = Cool
5 = Night Purge
6 = Precool
7 = Off
8 = Test
9 = Emergency Heat
10 = Fan Only
11 = Free Cool
12 = Ice Making
13 = Max Heat
14 = Economy Mode
15 = Dehumidifying
16 = Calibrate
1 = Flow
2 = No Flow
3 = Auto

Advertisement