Trane BCI-I Integration Manual page 22

Bacnet communication interface for intellipak and commercial self-contained
Table of Contents

Advertisement

Table 2.
Descriptions and configurations (continued)
Object
Type
Required Properties Read
Multistate
• Object_Identifier
Input
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Number_Of_States
Multistate
• Object_Identifier
Output
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Number_Of_States
• Priority_Array
• Relinquish Default
Multistate
• Object_Identifier
Value
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Number_Of_States
Notification
• Object_Identifier
Class
• Object_Name
• Object_Type
• Notification_Class
• Priority
• Ack_Required
• Recipient_List
Trend
• Object_Identifier
• Object_Name
• Object_Type
• Log_Enable
• Stop_When_Full
• Buffer_Size
• Log_Buffer
• Record_Count
• Total_Record_Count
• Event_State
(a)Properties written for Present_Value and Reliability only if Out_of_Service is TRUE.
ACC-SVP01B-EN • BCI-I Integration Guide
BACnet Data Points and Configuration Property Definitions
(a)
Properties Written
• Object_Name
• Description
• State_Text
• Out_Of_Service
• Present_Value
• Reliability
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
• Notify_Type
• Object_Name
• Description
• State_Text
• Out_Of_Service
• Present_Value
• Reliability
• Time_Delay
• Notification_Class
• Event_Enable
• Notify_Type
• Object_Name
• Description
• State_Text
• Out_Of_Service
• Present_Value
• Reliability
• Priority_Array
• Relinquish_Default
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
• Notify_Type
• Object_Name
• Priority
• Ack_Required
• Recipient_List
• Object_Name
• Log_Enable
• Start_Time
• Stop_Time
• Log_DeviceObjectProperty
• Log_Interval
• Stop_When_Full
• Buffer_Size
• Log_Buffer
• Record_Count
• Notification_Threshold
• Notification_Class
• Event_Enable
• Notify_Type
Optional Properties Read
• State_Text
• Reliability
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• State_Text
• Reliability
• Relinquish_Default
• Time_Delay
• Notification_Class
• Feedback_Values
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• State_Text
• Reliability
• Relinquish_Default
• Time_Delay
• Notification_Class
• Alarm_Values
• Fault_Values
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
None
• Start_Time
• Stop_Time
• Log_DeviceObjectProperty
• Log_Interval
• Stop_When_Full
• Buffer_Size
• Notification_Threshold
• Records_Since_Notification
• Last_Notify_Record
• Notification_Class
• Event_Enable
• Acked_Transitions
• Event_Time_Stamps
Ability
to
Ability to
Create
Delete
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects