Trane BCI-I Integration Manual page 31

Bacnet communication interface for intellipak and commercial self-contained
Table of Contents

Advertisement

Object Data Points and Diagnostic Data Points
Table 7.
Multistate Input (continued)
BCI-I Object
Identifier
Object Name
Multi-State Input, 32
Heat Output 4
Multi-State Input, 33
Heat Output 5
Multi-State Input, 34
Prefilter Status
Multi-State Input, 35
Primary Filter Status
Multi-State Input, 36
Final Filter Status
Multi-State Input, 37
Supply Fan Proving Status Indicates the current state of the supply fan.
Multi-State Input, 38
Exhaust Fan Status
Exhaust Fan Proving
Multi-State Input, 39
Status
Multi-State Input, 40
Return Fan Proving Status Indicates the current state of the return fan.
Multi-State Input, 41
Supply Fan Status
Multi-State Input, 42
Return Fan Status
Outdoor Air Damper
Multi-State Input, 43
Status
Multi-State Input, 44
Economizer System Status
Table 8.
Binary Output
Object Identifier
Binary Output, 1
Binary Output, 5
Binary Output, 6
Binary Output, 7
Binary Output, 8
Binary Output, 12
Binary Output, 13
Binary Output, 14
30
Description
Indicates the commanded state of heating
output 4.
Indicates the commanded state of heating
output 5.
Indicates the prefilter media state.
Indicates the primary filter media state.
Indicates the final filter media state.
Indicates the commanded state of the
exhaust fan.
Indicates if the unit exhaust fan is off or on.
Indicates the state of the supply fan.
Indicates the state of the return fan.
Indicates the operating state of the outdoor
damper.
Indicates the operating state of the
waterside economizer system.
Object Name
System Control Command
Heat Lockout Command
Cool Lockout Command
Economizer Minimum Position Command
Supply Fan Configuration Command
Heat or Reheat Enable Command
Filter Timer Reset Command
Diagnostic Reset Command
Object States
1 = Off
2 = On
3 = Not Present
1 = Off
2 = On
3 = Not Present
1 = Clean
2 = Dirty
3 = Not Present
1 = Clean
2 = Dirty
3 = Not Present
1 = Clean
2 = Dirty
3 = Not Present
1= Off
2= On
3= Not Present
1 = Off
2 = On
3 = Not Present
1= Off
2= On
3= Not Present
1= Off
2= On
3= Not Present
1 = Off
2 = On
3 = Not Present
1 = Off
2 = On
3 = Not Present
1 = At or Below Minimum Position
2 = Above Minimum Position
3 = Not Present
1 = Disabled
2 = Enabled
3 = Not Present
Description
Command the unit to standalone-
or BAS-controlled operation.
Command the unit to prevent
heating operation.
Command the unit to prevent
cooling operation.
Command the unit to the minimum
position operation.
Command the unit supply fan to
cycling or continuous operation.
Enable the heating or reheating
system during dehumidification
mode.
Command the unit to reset the
accumulated filter run hours.
Command the unit to reset and
clear diagnostics.
Relinquish
Default
Object States
Inactive = Standalone Control
Inactive
Active = BAS Control
Inactive = Allow Heating
Inactive
Active = Heating Locked Out
Inactive = Allow Cooling
Inactive
Active = Cooling Locked Out
Inactive = Disabled
Inactive
Active = Enabled
Inactive = Auto
Inactive
Active = On
Inactive = Disabled
Inactive
Active = Enabled
Inactive = Accumulating
Inactive
Active = Reset
Inactive = Normal
Inactive
Active = Reset
ACC-SVP01B-EN • BCI-I Integration Guide