BACnet Data Points and Configuration Property Definitions
Table 2.
Descriptions and configurations (continued)
Object
Type
Required Properties Read
Binary
• Object_Identifier
Output
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Polarity
• Priority_Array
• Relinquish_Default
Binary
• Object_Identifier
Value
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Polarity
Device
• Object_Identifier
• Object_Name
• Object_Type
• System_Status
• Vendor_Name
• Vendor_Identifier
• Model_Name
• Firmware_Revision
• Application_Software_Version
• Protocol_Version
• Protocol_Revision
• Protocol_Services_Supported
• Protocol_Object_Types_Supported
• Object_List
• Max_APDU_Length_Accepted
• Segmentation_Supported
• APDU_Timeout
• Number_Of_APDU_Retries
• Device_Address_Binding
• Database_Revision
Event
• Object_Identifier
Enrollment
• Object_Name
Object
• Object_Type
• Event_Type
• Notify_Type
• Event_Parameters
• Object_Property_Reference
• Event_State
• Event_Enable
• Acked_Transitions
• Notification_Class
• Event_Time_Stamps
20
(a)
Properties Written
• Object_Name
• Description
• Out_Of_Service
• Inactive_Text
• Active_Text
• Present_Value
• Reliability
• Change_Of_State_Count
• Elapsed_Active_Time
• Minimum_On_Time
• Minimum_Off_Time
• Relinquish_Default
• Time_Delay
• Notification_Class
• Event_Enable
• Acked_Transitions
• Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Inactive_Text
• Active_Text
• Present_Value
• Reliability
• Change_Of_State_Count
• Elapsed_Active_Time
• Minimum_On_Time
• Minimum_Off_Time
• Relinquish_Default
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
• Notify_Type
• Object_Name
• Location
• Description
• APDU_Segment_Timeout
• APDU_Timeout
• Number_Of_APDU_Retries
• Backup_Failure_Timeout
• Object_Name
• Notify_Type
• Event_Parameters
• Object_Property_Reference
• Event_Enable
• Notification_Class
Optional Properties Read
• Description
• Inactive_Text
• Active_Text
• Change_Of_State_Time
• Change_Of_State_Count
• Time_Of_State_Count_Reset
• Elapsed_Active_Time
• Time_Of_Active_Time_Reset
• Minimum_On_Time
• Minimum_Off_Time
• Time_Delay
• Notification_Class
• Feedback_Value
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Reliability
• Description
• Inactive_Text
• Active_Text
• Change_Of_State_Time
• Change_Of_State_Count
• Time_Of_State_Count_Reset
• Elapsed_Active_Time
• Time_Of_Active_Time_Reset
• Priority_Array
• Relinquish_Default
• Minimum_On_Time
• Minimum_Off_Time
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Reliability
• Location
• Description
• Max_Segments_Accepted
• APDU_Segment_Timeout
• Max_Master
• Max_Info_Frames
• Local_Time
• Local_Date
• Configuration_Files
• Last_Restore_Time
• Backup_Failure_Timeout
• Active_COV_Subscriptions
• None
ACC-SVP01B-EN • BCI-I Integration Guide
Ability
to
Ability to
Create
Delete
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects
None
None
Yes
Yes, only
user created
objects