Table 7.
Multistate Input (continued)
BCI-I Object
Identifier
Object Name
Economizer Decision
Multi-State Input, 15
Method
Multi-State Input, 17
Cooling Reset Type Status Indicates the type of cooling reset.
Multi-State Input, 18
Heating Reset Type Status Indicates the type of heating reset.
Multi-State Input, 19
Application Mode Status
Multi-State Input, 20
Occupancy Mode Status
Multi-State Input, 21
Unit Stop Source
Multi-State Input, 22
Cooling Setpoint Source
Multi-State Input, 23
Heating Setpoint Source
Multi-State Input, 24
Timed Override Status
Multi-State Input, 25
Cool Output 1
Multi-State Input, 26
Cool Output 2
Multi-State Input, 27
Cool Output 3
Multi-State Input, 28
Cool Output 4
Multi-State Input, 29
Heat Output 1
Multi-State Input, 30
Heat Output 2
Multi-State Input, 31
Heat Output 3
ACC-SVP01B-EN • BCI-I Integration Guide
Object Data Points and Diagnostic Data Points
Description
Unit method to determine when the
economizer system is enabled.
Indicates the current application mode of
the equipment.
Indicates the current occupancy mode of
the unit.
Source of the stop command that turned off
the equipment.
Indicates the source of the space cooling
setpoint.
Indicates the source of the space heating
setpoint.
Timed override request or cancel from zone
sensor.
Indicates the commanded state of cooling
output 1.
Indicates the commanded state of cooling
output 2.
Indicates the commanded state of cooling
output 3.
Indicates the commanded state of cooling
output 4.
Indicates the commanded state of heating
output 1.
Indicates the commanded state of heating
output 2.
Indicates the commanded state of heating
output 3.
Object States
1= Absolute Temperature
2= Relative Temperature
3= Absolute Enthalpy
4= Comparative Enthalpy
1= None
2= Outdoor Air
3= Zone
1= None
2= Outdoor Air
3= Zone
1 = Auto
2 = Heat
3 = Morning Warm-up
4 = Cool
5 = Night Purge
6 = Pre Cool
7 = Off
8 = Test
9 = Emergency Heat
10 = Fan Only
11 = Free Cool
12 = Ice-Making
13 = Max Heat
14 = Economy Mode
15 = Dehumidifying
16 = Calibrate
1 = Occupied
2 = Unoccupied
3 = Occupied Bypass
4 = Occupied Standby
1= None
2= Emergency Stop
3= External Auto/Stop
4= Local HI
5= Remote HI
1= RTM Zone Sensor
2= Night Setback Panel
3= Human Interface
4= GBAS 0-5V
5= BAS/Network
6= GBAS 0-10V
1= RTM Zone Sensor
2= Night Setback Panel
3= Human Interface
4= GBAS 0-5V
5= BAS/Network
6= GBAS 0-10V
1 = Idle
2 = On
3 = Cancel
1 = Off
2 = On
3 = Not Present
1 = Off
2 = On
3 = Not Present
1 = Off
2 = On
3 = Not Present
1 = Off|
2 = On
3 = Not Present
1 = Off
2 = On
3 = Not Present
1 = Off
2 = On
3 = Not Present
1 = Off
2 = On
3 = Not Present
29