Trane BCI-I Integration Manual page 15

Bacnet communication interface for intellipak and commercial self-contained
Table of Contents

Advertisement

BCI IntelliPak Rotary Switches and LEDs
Table 1.
LED Activities and Troubleshooting Tips
LED Name
Link and IMC
Service
Binary 01 to Binary 09
14
Indication or Troubleshooting
Activities
Blinks at the data transfer rate when the
TX blinks green
unit transfers data to other devices on
the link
Blinks at the data transfer rate when the
unit receives data from other devices on
the link
RX blinks yellow
• ON solid yellow; indicates there is
reverse polarity
Indicates that the controller is not
detecting communication
LED not lit
• Not lit; cycle the power to reestablish
communication
Indicates someone is pressing this LED
Shows solid green
or the controller is not operating
normally
Indicates controllers is not accessing
application software
Blinks green
• Restore; using TU service tool
Indicates controller is operating normally
LED not lit
Tip (Denoted in Bullets)
ACC-SVP01B-EN • BCI-I Integration Guide
Notes
TX LED: Regardless of connectivity or
not, this LED will constantly blink as it
continually looks for devices to
communicate to.
LED not lit:
Determine if, for example, a Tracer SC or
BACnet device is trying to talk to the
controller or if it is capable of talking to
the controller. Also determine if the
communication status shows down all of
the time.
Refer to
"Ground Measurements," p. 16
for a check-out procedure.
Press and hold during power up to place
controller into boot code or press and
hold for a count of approximately 10
seconds to clear the Device ID.
What is Boot Code? When the UC400
is placed into boot code, the system
will not run any applications such as
trending, scheduling, and TGP2
runtime.
Not Used