GEM 533 Operating Instructions Manual page 11

Esystep motorized globe valve
Table of Contents

Advertisement

7.5 Mechanical data
Protection class:
Weight:
Mechanical environ-
mental conditions:
Vibration:
Shock:
7.6 Duty cycle and service life
Service life:
Duty cycle:
▶ The specified characteristics and values apply to the factory setting.
▶ With reduced forces, higher duty cycles and/or higher ambient temperatures are possible. At higher force settings the duty
cycle and/or ambient temperature is reduced.
▶ IO-Link: Index 0x90 - Subindex 2 - Force
www.gemu-group.com
IP 65 acc. to EN 60529
Actuator
Actuator size 0 (code 0A)
Actuator size 1 (code 1A)
Valve body
DN
Weight
15
2.2
20
3.0
25
3.7
32
5.3
40
6.3
50
8.4
Weights in kg
Class 4M8 acc. to EN 60721-3-4:1998
5g acc. to IEC 60068-2-6 Test Fc
25g acc. to 60068-2-27 Test Ea
At least 500,000 switching cycles at room temperature and permissible duty cycle.
Control module Open/Close control (code AE, A5, A6)
Duty cycle with full valve lift and playing time 10 minutes.
100
90
80
70
60
50
40
30
Globe valve DN 15 - 25 (code 0A)
20
Globe valve DN 15 - 50 (code 1A)
10
0
0
10
20
Ambient temperature [°C]
0.95 kg
1.88 kg
30
40
50
60
70
NOTICE
11 / 55
7 Technical data
80
GEMÜ 533 eSyStep
OPEN / CLOSE (Code AE)

Advertisement

Table of Contents
loading

This manual is also suitable for:

533 esystep

Table of Contents