Limitation Of Modulation Range; End Of Operating Position - Siemens LMV36.520A1 Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

118/248
Building Technologies Division
Infrastructure & Citiies Sector

11.4.6 Limitation of modulation range

If the modulation range for stage 1 and stage 2, or stage 3, shall be further restricted, 4
parameters can be used to define a new low-fire and high-fire position.
No.
Parameter
Lower output limit
545
undefined = 20 %
Fuel 1: Lower output limit
565
undefined = 20 %
546
Upper output limit
undefined = 100 %
566
Fuel 1: Upper output limit
undefined = 100 %

11.5 End of operating position

When there is no more heat request, the system switches to phase 62. Here, the burner
runs down to low-fire as long as possible before the valves are shut.
The available period of time can be set via parameter 212. If this time is set to the
minimum value, the burner is immediately shut down if there is no more request for
heat. If the time exceeds 32 seconds, the burner always runs to low-fire. Naturally, it is
also possible to set intermediate times.
No.
Parameter
212
Max. time down to low-fire
Basic documentation LMV36...
11 Electronic fuel-air ratio control
CC1P7544en
25.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Agm60.4a9

Table of Contents