Siemens LMV36.520A1 Basic Documentation page 216

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Par.
Parameter
no.
LMV36...
Setting values
0 = 9600
1 = 19200
147
Setting of parity for Modbus communication
Setting value
0 = none
1 = odd
2 = even
148
Default output if communication with building automation is interrupted
Setting values
For modulation operation the setting range is as follows:
0...19.9 = burner off
20...100 = 20...100% burner rating
For multistage operation apply to setting range:
0 = burner OFF, P1, P2, P3
Invalid = no default output predefined by building automation
Default setting: Invalid
149
Fuel 1: Default output if communication with building automation is
interrupted
Setting values
For modulation operation the setting range is as follows:
0...19.9 = burner off
20...100 = 20...100% burner rating
For multistage operation apply to setting range:
0 = burner OFF, P1, P2, P3
Invalid = no default output predefined by building automation
Default setting: Invalid
161
Number of faults
162
Operating hours resettable
216/248
Building Technologies Division
Infrastructure & Citiies Sector
Number of
Type
Edit
elements
1
Selection
Edit
1
Output
Edit / clear
1
Output
Edit / clear
1
Std_u16
Read only
1
Std_s32
Reset
Basic documentation LMV36...
29 Parameter list LMV36...
Value range
Resolution
Min
Max
0
2
1
0%
100%
0.1%
0%
100%
0.1%
0
65535
1
0 h
9999999 h
1 h
Default
Password level
setting
0
SO
undefined
SO (BA)
undefined
SO (BA)
0
Info / Service
0 h
Info / Service
CC1P7544en
25.09.2013