24.1.2.3. List of phase displays

Phase
Function
Ph00
Lockout phase
Ph02
Safety phase
Ph10
Home run
Ph12
Standby (stationary)
Ph22
Fan ramp up time (122) (fan motor = ON, safety valve = ON)
Ph24
Traveling to the prepurge position
Ph30
Prepurge time
Ph36
Traveling to the ignition position
Ph38
Preignition time
Ph39
Valve proving filling time
(test pressure-switch-min when mounted between fuel valve V1 and fuel valve V2)
Ph40
1st safety time (ignition transformer ON)
Ph42
1st safety time (ignition transformer OFF),
Ph44
Interval 1
Ph50
2nd safety time
Ph52
Interval 2
Ph60
Operation 1 (stationary)
Ph62
Max. time low-fire (operation 2, preparing for shutdown, traveling to low-fire)
Ph70
Afterburn time
Ph72
Traveling to the postpurge position
Ph74
Postpurge time (no extraneous light test)
Ph78
Postpurge time 3 (abortion when load controller ON)
Ph80
Valve proving evacuation time
Ph81
Valve proving test time atmospheric pressure, atmospheric test
Ph82
Valve proving filling test, filling
Ph83
Valve proving test time gas pressure, pressure test
Ph90
Gas shortage waiting time
Building Technologies Division
Infrastructure & Citiies Sector
Basic documentation LMV36...
24 Operation of basic unit via the AZL2...
165/248
CC1P7544en