Connecting the power supply
The supply voltage is supplied over a 4-pin connector at the front of the SIMATIC Drive
Controller (behind the top of the front cover).
Use rigid or flexible cables with a conductor cross-section as specified in the SIMATIC Drive
Controller manual (https://support.industry.siemens.com/cs/ww/en/view/109766666) for
wiring the power supply.
Tighten the connector using a flat-blade screwdriver.
Note
• The 24 V DC cable must be approved for temperatures of up to 70 °C.
• The maximum permissible cable length is 10 m.
6.6

PROFINET and PROFIBUS DP

Connecting interfaces for communication
Connect the communication interfaces of the SIMATIC Drive Controller using standardized
plug connectors.
Use preassembled connecting cables for the connection.
If you want to assemble the communication cables yourself, we recommend cables and
RJ45 plug connectors from the Siemens FastConnect system.
Note
The X130 interface of the SIMATIC Drive Controller supports 10, 100 and 1000 Mbps.
For 1000 Mbps, you need 8-wire cables (4x2) and the 1000 Mbit version of the 180°
FastConnect connector.
The 145° FastConnect connectors can only be used for Ethernet interface X130 with a max.
of 100 Mbps.
SIMATIC Drive Controller
System Manual, 11/2019, A5E46600094-AA
6.6 PROFINET and PROFIBUS DP