Test Run and Operation Data

3. Test Run and Operation Data

3.1

General Operation Data

Guide Lines for
The operation value guide lines when operating under standard conditions (at Rated
frequency) by pushing the test run button on the remote controller are as given in the table
Optimal
below.
Operation
Condition
Indoor Unit Fan:
"H" Operation Compressor: Rated Frequency
Cooling
Heating
116
High
Low
Discharge
Pressure
Pressure
Pipe
(Mpa)
(Mpa)
Temperature
(°C)
26 bar ~
6 bar ~
60~100
34 bar
10 bar
25 bar ~
5.3 bar ~
60~100
32.6 bar
7.5 bar
Suction
Indoor Unit
Temperature
Side:
(°C)
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(°C)
–2~10
8~18
–6~2
14~30
SiBE28-804
Outdoor Unit
Side:
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(°C)
7~12
2~6
Test Operation