SiBE28-804
2.2
Stacked
The illustration below shows the required installation and service space (mm). The values in
brackets are for RZQ100~140, RZQS125~140 class.
2.3
Multiple Rows
The illustration below shows the required installation and service space (mm). The values in
brackets are for the 100~140 class.
Relation of dimensions of H, A and L are shown in the table below.
L ≤ H
H < L
Appendix
Installation and Service Space (RZQ100~140C7, RZQS125~140C7)
Do not stack more than one unit.
± 100 mm is required as the dimension for laying the upper outdoor unit's drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
Obstacles exist in front of the outlet side
Installation of one unit per row
Obstacles exist in front of the air inlet
Installing multiple units (2 units or more)
in lateral connection per row
L
0 < L ≤ 1/2H
1/2H < L
installation impossible
A
150 (250)
200 (300)
245