SiBE28-804
Capacity
When "low humidity application" is selected. Field setting 16(26)-2-03:
Outdoor
Temp.
11
(°C-DB)
-15
0.62
-10
0.62
-5
0.62
0
0.62
5
0.62
10
0.62
15
0.62
20
0.62
25
0.62
30
0.61
35
0.61
40
0.61
Capacity
When "low humidity application + freeze up operation prevention" is selected. Field setting
16(26)-2-04:
Outdoor
Temp.
11
(°C-DB)
-15
0.51
-10
0.51
-5
0.51
0
0.51
5
0.51
10
0.51
15
0.51
20
0.51
25
0.51
30
0.51
35
0.51
40
0.51
Note:
• Operation range on indoor side expanded from minimum 12°CWB to 11°CWB when using LH
• Do not use a setpoint below 20°C to avoid operation out of the indoor operation range
• Be sure to set the indoor fan to high speed.
2.14 Defrost Start Setting
Refer to 'Defrost Operation' on P47.
Test Operation
14
16
Capacity (% of standard point)
0.76
0.86
0.76
0.86
0.81
0.91
0.81
0.91
0.81
0.91
0.81
0.91
0.81
0.91
0.81
0.91
0.81
0.91
0.81
0.91
0.81
0.94
0.81
0.90
14
16
Capacity (% of standard point)
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.68
0.78
0.67
0.78
setting.
(11°CWB).
Indoor Temp. (°C-WB)
18
19
0.95
1.00
0.95
1.00
1.01
1.06
1.01
1.06
1.01
1.06
1.01
1.06
1.01
1.12
1.07
1.10
1.05
1.07
1.01
1.04
0.98
1.00
0.94
0.96
Indoor Temp. (°C-WB)
18
19
0.95
1.01
0.95
1.01
0.95
1.01
0.95
1.01
0.95
1.01
0.95
1.01
0.95
1.01
0.95
1.01
0.95
1.00
0.95
1.00
0.95
1.00
0.94
0.96
Field Settings
20
22
1.02
1.07
1.02
1.07
1.16
1.21
1.16
1.21
1.16
1.21
1.16
1.21
1.14
1.19
1.12
1.16
1.09
1.13
1.06
1.10
1.02
1.06
0.98
1.02
20
22
1.06
1.16
1.06
1.16
1.06
1.16
1.06
1.16
1.06
1.16
1.06
1.16
1.06
1.16
1.06
1.16
1.06
1.13
1.05
1.10
1.02
1.06
0.98
1.02
24
1.11
1.11
1.26
1.26
1.26
1.26
1.24
1.21
1.18
1.14
1.11
1.06
24
1.26
1.26
1.26
1.26
1.26
1.26
1.24
1.21
1.18
1.14
1.11
1.06
115