Daikin SkyAir Service Manual page 47

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

General Functionality
Step
4
5
Active
components
Component
Compressor
4-way valve
Outdoor unit fan
Indoor unit fan
Drain pump
Additional info
36
Action
Set the emergency switch on the outdoor PCB to the forced mode you prefer (Cooling or
Heating).
EMERGENCY
ON
COOL
1
2
3
4
OFF
HEAT
Turn ON the power supply.
Forced cooling
ON
OFF
H fan speed
H fan speed
ON
During emergency operation, do not attempt to operate the equipment from the remote
controller. The remote controller shows "88" while the emergency operation is active on the
indoor unit
If a safety device is activated during emergency, all actuators are turned OFF
In cooling, the unit runs for 20min and then stops for 10min in order to avoid freeze-up of the
indoor coil.
In heating, defrost is activated for 3 minutes once every hour.
Emergency operation can not be carried out when the PC board itself is defective.
Be sure to set the emergency switch on both the outdoor and indoor unit.
The unit will not regulate the temperature during emergency operation.
Change the position of the emergency switch only when the power is turned off.
Forced heating
Forced defrosting
ON
ON
ON
OFF
H fan speed
OFF
H fan speed
H fan speed
ON
ON
SiBE28-804