Daikin SkyAir Service Manual page 238

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

SiBE28-804
Check No.3
Checking the Thermistors
Thermistors
If the cause of the problem is related to the thermistors, then the thermistors should be checked
prior to changing the PC board.
For more information about these thermistors, see:
Overview of
The table below contains an overview of the thermistors:
thermistors
Thermistor
Indoor
Outdoor
Checking
To check the thermistors, proceed as follows:
Troubleshooting
"Wiring Diagrams'' (outdoor units)
"Functions of Thermistors" on P33.
Step
Action
1
Disconnect the thermistor from the PC board.
2
Read the temperature and the resistor value.
3
Check if the measured values correspond with the values in the table on the next pages.
Troubleshooting by Remote Controller Display / LED Display
Description
R1T
Suction air thermistor
R2T
Heat exchanger thermistor
R1T
Ambient air thermistor
R2T
Discharge pipe thermistor
R3T
Suction pipe thermistor
R4T
Heat exchanger thermistor
R5T
Intermediate heat exchanger thermistor
R6T
Liquid pipe thermistor
R10T
Power module fin thermistor
227