Daikin SkyAir Service Manual page 123

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

Field Settings
Graph 1
Target evaporating temperature control in case of factory setting 16(26)-2-01:
Note:
Te by LP sensor
112
Te target acceptable area
Remote controller setting temp.
Te target limitted
≤ Indoor temp. – 11˚
(not to rising wetbulb)
Te target limitted ≥ 2˚C
(not to freeze)
RZQ71~140C7V1B,
RZQS71~140C7V1B
Te target limitted ≤ 20˚C
(to protect the comp.)
Te (see note) target
acceptable area
Indoor temp. > setting
→ Te target down
Indoor temp. < setting
→ Te target up
Freeze protection
(40min. integrated coil temp. ≤ -1˚C)
SiBE28-804
Te target limitted
≥ Indoor temp. – 25˚
(not to sweat)
Indoor Temp
(˚C DB)