SiBE28-804
Possible system
The table below contains the possible system settings, which are displayed on the remote
controller if the TEST button is pushed twice shortly.
settings
Size
Settings
Changing the
To enter the monitoring level and to change the maintenance mode settings, proceed as
follows:
mode settings
Test Operation
Display
35
35
45
45
60
63
71
71
100
100
125
125
140
140
200
200
250
250
Step
Action
1
Hold down the INSPECTION/TEST button for at least 4 s to enter the field setting mode.
2
Hold down the INSPECTION/TEST button for at least 4 s to enter the maintenance
mode.
3
Press the TEMPERATURE CONTROL buttons as many times as needed to select the
mode No. you want.
4
Press the TIMER SELECTION button as many times as needed to select the unit No.
you want.
5
Carry out the settings for modes 44 and 45. See "Maintenance Mode Settings" further
in this section.
6
Press the CONFIRMATION button to confirm the settings of modes 44 and 45.
7
Press the INSPECTION/TEST button to return to the normal operating mode.
Type
Settings
Display
FCQ-C
FHQ
FAQ
FFQ
FBQ
FUQ
FDQ
FVQ
Field Settings
5FA
5HJ
5AL
56J
5JJ
53J
5JJ
51
97