Daikin SkyAir Service Manual page 124

R-410a, 50hz
Hide thumbs Also See for SkyAir:
Table of Contents

Advertisement

SiBE28-804
Graph 2
Target evaporating temperature control when "low humidity application" is selected. Field
setting 16(26)-2-03:
Note:
Te by LP sensor
Test Operation
Te target acceptable area
Remote controller setting temp.
Te target
Te target limitted ≤ 20˚C
(˚C)
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp. > setting → Te target down
Indoor temp. < setting → Te target up
RZQ71~140C7V1B,
RZQS71~140C7V1B
Te target limitted ≥ 0˚C
Freeze protection
(40min. integrated coil temp. ≤ -1˚C)
Field Settings
Indoor Temp
(˚C DB)
113