Carbon Monoxide Poisoning - Carrier 100/A Series Installation, Start-Up, Operating And Service And Maintenance Instructions

4-way multipoise, inducted-combustion gas furnace, input capacities: 45,000 thru 135,000 btuh
Table of Contents

Advertisement

CARBON MONOXIDE POISONING
HAZARD
Failure
to
follow
the
steps
outlined
below
for
each
appliance
connected
to the venting
system
being placed
into
operation
could
result
in carbon
monoxide
poisoning
or
death.
The
following
steps
shall
be
followed
for each
appliance
connected
to the venting
system
being placed
into
operation,
while
all other
appliances
connected
to
the
venting
system
are not in operation:
1. Seal any unused
openings
in venting
system.
2. Inspect
the
venting
system
for
proper
size
and
horizontal
pitch, as required
in the National
Fuel Gas
Code,
ANSI
Z223.1/NFPA
54
or CSA
B149.1,
Natural
Gas and Propane
Installation
Code and these
instructions.
Determine
that there is no blockage
or
restriction,
leakage,
corrosion
and other deficiencies,
which
could cause an unsafe condition.
3. As far as practical,
close
all building
doors
and
windows
and all doors
between
the space
in which
the appliance(s)
connected
to the venting
system
are
located
and other spaces
of the building.
4. Close fireplace
dampers.
5. Turn
on
clothes
dryers
and
any
appliance
not
connected
to
the
venting
system.
Turn
on
any
exhaust
fans,
such
as range
hoods
and bathroom
exhausts,
so they are operating
at maximum
speed.
Do not operate
a summer
exhaust
fan.
6. Follow
the lighting
instructions.
Place the appliance
being
inspected
into operation.
Adjust the thermostat
so appliance
is operating
continuously.
7. Test
for
spillage
from
draft
hood
equipped
appliances
at the draft
hood
relief opening
after 5
nfinutes
of main burner
operation.
Use the flame of a
match or candle.
8. If improper
venting
is observed
during
any of the
above tests, the venting
system
must be corrected
in
accordance
with the National
Fuel Gas Code, ANSI
Z223.1/NFPA
54 and/or
CSA
B149.1,
Natural
Gas
and Propane
Installation
Code.
9. After
it has
been
deternfined
that
each
appliance
connected
to the venting
system
properly
vents when
tested
as outlined
above,
return
doors,
windows,
exhaust
fans,
fireplace
dampers
and
any
other
gas-fired
burning
appliance
to
their
previous
conditions
of use.
Vent system or vent connectors may need to be resized. Vent
systems or vent connectors, must be sized to approach nfinimum
size as deternfined using appropriate table found in the NFGC or
CAN/CSA-BI49.1-05.
GENERAL
VENTING
REQUIREMENTS
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National Fuel
Gas Code ANSI Z223.1-2006/NFPA
54-2006 (NFGC), Parts 12
and 13 in the United States or the National Standard of Canada,
Natural Gas and Propane
Installation
Code CSA-B149.1-05
(CAN/CSA-B149.1-05),
Section 8 and Appendix C in Canada,
the local
building
codes,
and furnace
and vent manufacturers'
instructions.
These
furnaces
are design-certified
as Category
I furnaces
in
accordance
with ANSI
Z21.47-2006/CSA
2.3-2006
and operate
with a non-positive
vent static pressure
to nfininfize
the potential
for vent gas leakage.
Category
I furnaces
operate
with a flue loss
not
less
than
17
percent
to
nfininfize
the
potential
for
condensation
in the venting
system.
These furnaces
are approved
for
common
venting
and
multistory
venting
with
other
fan
assisted or draft hood equipped
appliances
in accordance
with the
NFGC
or the CAN/CSA-BI49.1-05,
the local
building
codes,
and furnace
and vent manufacturers'
instructions.
The following
information
and warning
must be considered
in addition
to the
requirements
defined
in
the
NFGC
and
the
CAN/CSA-B149.1-05.
1. If a vent
(common
or dedicated)
becomes
blocked,
the
furnace
will be shut
off by the draft
safeguard
switch
located
on the vent elbow.
2. Do not vent this
Category
I furnace
into a single-wall
dedicated
or common
vent.
The
dedicated
or common
vent is considered
to be the vertical
portion
of the vent
system
that terminates
outdoors.
3. Vent connectors
serving
Category
I furnaces
shall not be
connected
into any portion
of a mechanical
draft system
operating
under positive
pressure.
4. In the U.S.: Do not vent this appliance
with any solid fuel
burning
appliance.
In Canada:
Check
with
the authority
having
jurisdiction
for approval
on use with
solid
fuel
burning
appliance.
5. Category
I furnaces
must
be vented
vertically
or nearly
vertically
unless
equipped
with a listed power
ventor.
6. Do
not vent
this
appliance
into
an
unlined
masonry
chimney.
Refer to Chimney
Inspection
Chart, Fig. 33.
MASONRY
CHIMNEY
REQUIREMENTS
NOTE:
These
furnaces
are CSA
design-certified
for use
in
exterior
tile-lined
masonry
chimneys
with
a factory
accessory
Chimney
Adapter
Kit. Refer to the furnace
rating plate for correct
kit usage.
The Chimney
Adapter
Kits are for use with
ONLY
furnaces
having
a Chimney
Adapter
Kit numbers
marked
on the
furnace
rating plate.
If a clay
tile-lined
masonry
chimney
is being
used
and it is
exposed
to the outdoors
below
the roof line, relining
might
be
required.
Chimneys
shall conform
to the Standard
for Chimneys,
Fireplaces,
Vents,
and
Solid
Fuel
Burning
Appliances
ANSI/NFPA
211-2006
in the United
States and to a Provincial
or
Territorial
Building
Code in Canada
(in its absence,
the National
Building
Code of Canada)
and must be in good condition.
U.S.A.-Refer
to Sections
13.1.8
and
13.2.20
of the
NFGC
NFPA54/ANSI
Z223.1-2006
or the authority
having jurisdiction
to determine
whether
relining
is required.
If relining
is required,
use a properly
sized listed metal
liner,
Type-B
vent,
or a listed
alternative
venting
design.
NOTE:
See
the
NFPA54/ANSI
Z223.1-2006,
13.1.8
and
13.2.20
regarding
alternative
venting
design
and the Exception,
which
cover
installations
such
as the
Chimney
Adapter
Kits
KGACA02014FC
and KGACA02015FC,
which
are listed
for
use with these furnaces.
The Chimney
Adapter
Kit is listed alternative
venting
system
for
these furnaces.
See the kit instructions
for complete
details.
il
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents