Carrier 100/A Series Installation, Start-Up, Operating And Service And Maintenance Instructions page 51

4-way multipoise, inducted-combustion gas furnace, input capacities: 45,000 thru 135,000 btuh
Table of Contents

Advertisement

5.Heat p ump
(See Fig.25
-
32 for thermostat
connections.)
When
installed
with
a
heat
pump,
the
furnace
control
automatically
changes
the timing
sequence
to avoid long
blower
off times during
demand
defrost
cycles.
When the
R-to-
W-and-Y1
or R-to-W-and-Yl-and-G
circuits
are energized
the furnace
control
CPU
will switch
to or
turn on the blower
motor
BLWM
at HEAT
speed,
and
begin
a heating
cycle.
The
blower
motor
BLWM
will
remain
on until the end of the prepurge
period,
then shut
off for 24 seconds
then come
back
on at HEAT speed.
When
the W input signal
disappears,
the furnace
control
begins
a normal inducer
post-purge
period and the blower
remains
running
at
HEAT
speed
for
the
selected
blower-OFF
delay
period
then
switches
to low-cool
speed
(same
speed
as
FAN).
If
the
R-to-W-and-Yl-and-G
signals
disappear
at the
same
time,
the blower
motor
BLWM
will remain
on for the
selected
blower-OFF
delay
period.
If
the
R-to-
W-and-Y1
signals
disappear,
leaving
the G signal,
the
blower
motor
BLWM
will remain
on for the
selected
blower-OFF
delay
period
then
switch
to
continuous-blower
speed. When
the R-to-W-and-Y/Y2,
R-to-W-and-Y/Y2-and-G,
R-to-W-and-Yl-and-
Y/Y2,
or R-to-W-
and-Yl-and-Y/Y2-and-G
circuits
are energized
the furnace
control
CPU
will switch
to or
turn on the blower motor BLWM at HEAT speed, and
begin a heating cycle. The blower motor BLWM will
remain on until the end of the prepurge period, then shut
off for 24 seconds then come back on at HEAT speed.
When theWinput signal disappears, the furnace control
begins a normal inducer post-purge period and the blower
switches to COOL speed after a 3 second delay. If the
R-to-W-and-Y/Y2-and-G
or R-to-W-and-Yl-and
-
Y/Y2-and-G
signals disappear
at the same time, the
blower motor BLWM will remain on for the selected
blower-OFF
delay period. If the R-to-W-and-Y/Y2
or
R-to-W-and-Yl-and-Y/Y2
signals disappear,
leaving
the G signal, the blower motor BLWM will remain on for
the selected blower-OFF
delay period then switch to
continuous blower speed.
Wiring Diagrams
Refer to Fig. 59 for wiring diagram.
Troubleshooting
Refer to the service label. (See Fig. 55.) The Troubleshooting
Guide (See Fig. 60) can be a useful tool in isolating furnace
operation problems. Beginning with the word "Start," answer
each question and follow the appropriate arrow to the next item.
The Guide will help to identify the problem or failed component.
After
replacing
any
component,
verify
correct
operation
sequence.
il
51