Carrier 100/A Series Installation, Start-Up, Operating And Service And Maintenance Instructions page 50

4-way multipoise, inducted-combustion gas furnace, input capacities: 45,000 thru 135,000 btuh
Table of Contents

Advertisement

il
2. Cooling
Mode
The thermostat "calls for cooling."
a. Single-Speed
Cooling
(See Fig. 25 - 32 for thermostat
connections)
The thermostat
closes the R-to-G-and-Y
circuits. The
R-to-
Y
circuit
starts
the
outdoor
unit,
and
the
R-to-G-and-Y/Y2
circuits
start
the
furnace
blower
motor BLWM on COOL speed.
The electronic
air cleaner ternfinal
EAC-1
is energized
with 115 vac when the blower motor BLWM is operating.
When
the thermostat
is satisfied,
the R-to-G-and-Y
circuits are opened.
The outdoor
unit will stop, and the
furnace blower motor BLWM will continue operating
on
the COOL
speed for an additional
90 seconds.
Jumper
Y/Y2
to DHUM
to reduce
the cooling
off-delay
to 5
seconds.
(See Fig. 24.)
b. Two-Speed
Cooling
(See Fig. 25 - 32 for thermostat
connections.)
The thermostat
closes the R-to-G-and-Y1
circuits for
low-cooling
or closes
the R-to-G-and-Yl-and-Y2
circuits for high-cooling.
The R-to-Y1
circuit starts the
outdoor
unit
on
low-cooling
speed,
and
the
R-to-G-and-Y1
circuit starts the furnace
blower motor
BLWM on low-cool
speed (same speed
as FAN). The
R-to-Yl-and-Y2
circuits
start
the
outdoor
unit
on
high-cooling
speed, and the R-to-Gand-
Y/Y2 circuits
start the furnace blower
motor BLWM on COOL speed.
The electronic
air cleaner
ternfinal EAC-1
is energized
with
115 vac whenever
the blower
motor
BLWM
is
operating.
When the thermostat is satisfied, the R-to-G-and-Y1
or
R-to-G-and-Y1
and
Y2
circuits
are opened.
The
outdoor
unit stops, and the furnace
blower
BLWM and
electronic
air
cleaner
ternfinal
EAC-I
will
remain
energized
for an additional
90 seconds.
Jumper
YI
to
DHUM to reduce the cooling off-delay
to 5 seconds. (See
Fig. 24.)
3. Thermidistat
Mode
(See Fig. 26-29
for Thermidistat
connections.)
The dehunfidification
output,
DHUM
on the Thernfidistat
should
be connected
to the furnace
control
thermostat
ternfinal DHUM.
When there is a dehunfidify
demand,
the
DHUM
input
is activated,
which
means
24 vac signal is
removed
from the DHUM
input ternfinal.
In other words,
the DHUM
input
logic is reversed.
The DHUM
input
is
turned ON when
no dehunfidify
demand
exists. Once 24
vac is detected
by the furnace
control on the DHUM
input,
the furnace
control
operates
in Thernfidistat
mode.
If the
DHUM
input
is low for more than 48 hours,
the furnace
control
reverts back to non-Thernfidistat
mode.
The cooling
operation
described
in item
2. above
also
applies
to operation
with
a Thernfidistat.
The exceptions
are listed below:
a. When the R-to-G-and-Y1
circuit is closed and there is
a demand
for dehunfidification,
the furnace blower motor
BLWM will continue
running
at low-cool
speed (same
speed as FAN).
b. When the R-to-G-and-Y/Y2
circuit is closed and there
is a demand
for dehunfidification,
the furnace
blower
motor BLWM will drop the blower
speed from
COOL
to HEAT for a maxinmna
of 10 nfinutes
before reverting
back
to COOL
speed.
If there is still a demand
for
dehunfidification
after 20 nfinutes,
the furnace
control
CPU will drop the blower
speed back to HEAT speed.
This alternating
10- nfinute
cycle will continue
as long
as there is a call for cooling.
4.
c. When the "call for cooling" is satisfied and there is a
demand for dehunfidification,
the cooling blower-off
delay is decreased from 90 seconds to 5 seconds.
Continuous
Blower Mode
When the R-to-G
circuit is closed by the thermostat, the
blower motor BLWM will operate on continuous-blower
speed (can be adjusted to FAN, HEAT, or COOL speed) at
the thermostat. Factory default is FAN speed. Ternfinal
EAC-1 is energized as long as the blower motor BLWM is
energized. During a call for heat, the blower BLWM will
stop during igniter warm-up
(17 seconds), ignition (7
seconds), and blower-ON
delay (25 seconds), allowing
the furnace heat exchangers to heat up more quickly, then
restarts at the end of the blower-ON
delay period at HEAT
speed.
In heating, the furnace control CPU will hold the blower
motor
BLWM
at HEAT
speed
during
the selected
blower-OFF
delay
period
before
reverting
to
continuous-blower
speed. When the thermostat "calls for
low-cooling,"
the blower motor BLWM will switch to
operate at low-cool speed (same speed as FAN). When the
thermostat is satisfied, the blower motor BLWM will
operate an additional 90 seconds on low-cool speed (same
speed
as
FAN)
before
reverting
back
to
continuous-blower
speed.
When the thermostat "calls for high-cooling",
the blower
motor BLWM will operate at COOL speed. When the
thermostat is satisfied, the blower motor BLWM will
operate an additional 90 seconds on COOL speed before
reverting back to continuous-blower
speed.
When the R-to-G
circuit is opened, the blower motor
BLWM will
continue
operating
for an additional
5
seconds,
if no other function
requires blower motor
BLWM operation.
Continuous
Blower Speed Selection from Thermostat
-To select different continuous-blower
speeds from the
room thermostat, momentarily turn off the FAN switch or
pushbutton on the room thermostat for 1-3 seconds after
the blower motor BLWM is operating. The furnace control
CPU will shift the continuous-blower
speed from the
factory setting of FAN to HEAT speed. Momentarily
turning off the FAN switch again at the thermostat will
shift the continuous-blower
speed from HEAT to COOL.
Repeating the procedure will shift the continuous-blower
speed from COOL to FAN speed. The selection can be
changed as many times as desired and is stored in the
memory to be automatically
used following
a power
interruption.
5O

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents