Carbon Monoxide Poisoning; General Venting Requirements - Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance

Table of Contents

Advertisement

CARBON MONOXIDE POISONING
HAZARD
Failure
to
follow
the
steps
outlined
below
for
each
appliance
connected
to the venting
system
being placed
into
operation
could
result
in carbon
monoxide
poisoning
or
death.
The
following
steps
shall
be
followed
for each
appliance
connected
to the venting
system
being placed
into
operation,
while
all other
appliances
connected
to
the
venting
system
are not in operation:
1. Seal any unused
openings
in venting
system.
2. Inspect
the
venting
system
for
proper
size
and
horizontal
pitch, as required
in the National
Fuel Gas
Code,
ANSI
Z223.1/NFPA
54
and
these
instructions.
Determine
that there is no blockage
or
restriction,
leakage,
corrosion
and other deficiencies,
which
could cause an unsafe condition.
3. As far as practical,
close
all building
doors
and
windows
and all doors
between
the space
in which
the appliance(s)
connected
to the venting
system
are
located
and other spaces
of the building.
4. Close fireplace
dampers.
5. Turn
on
clothes
dryers
and
any
appliance
not
connected
to
the
venting
system.
Turn
on
any
exhaust
fans,
such
as range
hoods
and bathroom
exhausts,
so they are operating
at maximum
speed.
Do not operate
a summer
exhaust
fan.
6. Follow
the lighting
instructions.
Place the appliance
being
inspected
into operation.
Adjust the thermostat
so appliance
is operating
continuously.
7. Test
for
spillage
from
draft
hood
equipped
appliances
at the draft
hood
relief opening
after 5
minutes
of main burner
operation.
Use the flame of a
match or candle.
8. If improper
venting
is observed
during
any of the
above tests, the venting
system
must be corrected
in
accordance
with the National
Fuel Gas Code, ANSI
Z223.1/NFPA
54.
9. After
it has
been
determined
that
each
appliance
connected
to the venting
system
properly
vents when
tested
as outlined
above,
return
doors,
windows,
exhaust
fans,
fireplace
dampers
and
any
other
gas-fired
burning
appliance
to
their
previous
conditions
of use.
Vent system or vent connectors may need to be resized. Vent
systems or vent connectors must be sized to approach minimum
size as determined using appropriate table found in the NFGC.
GENERAL
VENTING
REQUIREMENTS
Follow all safety codes for proper vent sizing and installation
requirements, including local building codes, the National Fuel
Gas Code ANSI Z223.1-2009/NFPA
54-2009 (NFGC), Parts 12
and 13 in the United States, the local building codes, and furnace
and vent manufacturers'
instructions.
These furnaces are design-certified
as Category I furnaces in
accordance with ANSI Z21.47-2006/CSA
2.3-2006 and operate
with a non-positive vent static pressure to minimize the potential
for vent gas leakage. Category I furnaces operate with a flue loss
not less than 17% to minimize the potential for condensation in
the venting system. These furnaces are approved for common
venting and multi-story
venting with other fan assisted or draft
hood
equipped
appliances
in accordance
with the NFCG,
local
building
codes, and furnace
and vent manufacturers'
instructions.
The following
information
and warning
must be considered
in
addition
to the requirements
defined
in the NFGC.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death.
Do
not bypass
the draft
safeguard
switch,
as an unsafe
condition
could exist which must be corrected.
1. If a vent (common
or dedicated)
becomes
blocked,
the fur-
nace will be shut off by the draft safeguard
switch located
on the vent elbow.
2. Two-stage
furnaces
require
Type B vent
connectors
out-
side the casing in all configurations.
Single wall vent con-
nector
may
be used inside
the furnace
casing
with
the
transition
to Type B vent outside
the furnace
casing.
Size
the connector
so that the FAN-Min
vent connector
capa-
city is equal to or lower than the low fire rate of the fur-
nace and the FAN-Max
vent connector
capacity
is equal
to or higher than the furnace
high fire rate.
3. Do not vent this Category
I furnace into a single wall ded-
icated or common
vent. The dedicated
or common
vent is
considered
to be the vertical
portion
of the vent system
that terminates
outdoors.
4. Vent connectors
serving
Category
I furnaces
shall not be
connected
into any portion
of a mechanical
draft system
operating
under positive
pressure.
5. Do not vent this appliance
with any solid fuel burning
ap-
pliance.
6. Category
I furnaces
must
be vented
vertically
or nearly
vertically
unless equipped
with a listed mechanical
venter.
See the SIDEWALL
VENTING
section.
7. Do not vent this appliance
into an unlined
masonry
china-
ney. Refer to Chimney
Inspection
Chart, Fig. 34.
MASONRY
CHIMNEY
REQUIREMENTS
NOTE:
These
furnaces
are CSA
design-certified
for use
in
exterior
tile-lined
masonry
chimneys
with
a factory
accessory
Chimney
Adapter
Kit. Refer to the furnace
rating plate for correct
kit usage.
The Chimney
Adapter
Kits are for use with
ONLY
furnaces
having
a Chimney
Adapter
Kit number
marked
on the
furnace
rating plate.
If a clay
tile-lined
masonry
chimney
is being
used
and it is
exposed
to the outdoors
below
the roof line, relining
might
be
required.
Chimneys
shall conform
to the Standard
for Chimneys,
Fireplaces,
Vents,
and
Solid
Fuel
Burning
Appliances
ANSI/NFPA
211-2009
in the United
States and must be in good
condition.
U.S.A.-Refer
to Sections
13.1.8
and 13.2.20
of the NFPA
54 /
ANSI
Z223.1-2009
or
the
authority
having
jurisdiction
to
determine
whether
relining
is required.
If relining
is required,
use
a properly
sized
listed
metal
liner,
Type-B
vent,
or a listed
alternative
venting
design.
NOTE:
See the NFPA
54 / ANSI
Z223.1-2009,
13.1.8
and
13.2.20
regarding
alternative
venting
design
and the exception,
which
cover
installations
such
as the
Chimney
Adapter
Kits
which
are listed
for use with
these furnaces.
See Table 18 for
accessory
listing.
26

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents