Carrier 100 Series Service And Maintenance Procedures Manual

2-speed, 2-stage induced-combustion deluxe 4-way multipoise furnace, size 090

Advertisement

Visit www.carrier.com
Service and Maintenance Procedures
NOTE: Read the entire instruction manual before starting the
installation.
These procedures are for size 88,000 Btuh input unit.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS .....................................................1
INTRODUCTION ..........................................................................1
General ......................................................................................1
PROCEDURE ................................................................................2
CARE AND MAINTENANCE.....................................................2
Cleaning And/Or Replacing Air Filter.....................................2
Blower Motor and Wheel.........................................................3
Cleaning Heat Exchanger .........................................................4
Electrical Controls and Wiring.................................................5
WIRING DIAGRAMS...................................................................7
TROUBLESHOOTING .................................................................7
REGISTERED QUALITY SYSTEM
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. Observe precautions in
the literature, on tags, and labels attached to or shipped with the
unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA
54-1999/ANSI Z223.1-1999. In Canada, refer to the CAN/CGA-
B149.1- and .2-M95 National Standard of Canada, Natural Gas
and Propane Installation Codes (NSCNGPIC). Wear safety glasses
and work gloves. Have fire extinguisher available during start-up
and adjustment procedures and service calls.
This is the safety-alert symbol
the furnace and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 101
Catalog No. 535-80008
Tab 6a 8a
2-Speed, 2-Stage Induced-Combustion
Size 090, Series 100
CERTIFIED
®
. When you see this symbol on
Printed in U.S.A.
Deluxe 4-Way Multipoise Furnace
Fig. 1-Model 58CTS Multipoise
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
The ability to properly perform maintenance on this equip-
ment requires certain knowledge, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User's Manual. FAILURE
TO FOLLOW THIS WARNING COULD RESULT IN
POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS
PERSONAL INJURY, OR DEATH.
Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and dangerous
operation.
INTRODUCTION
Step 1-General
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
Form 58CTS-1SM
58CTS
A00353
Pg 1
11-00
Replaces: New

Advertisement

loading

Summary of Contents for Carrier 100 Series

  • Page 1: Table Of Contents

    58CTS 2-Speed, 2-Stage Induced-Combustion Deluxe 4-Way Multipoise Furnace Visit www.carrier.com Service and Maintenance Procedures Size 090, Series 100 NOTE: Read the entire instruction manual before starting the installation. These procedures are for size 88,000 Btuh input unit. TABLE OF CONTENTS SAFETY CONSIDERATIONS .............1...
  • Page 2: Electrostatic Discharge (Esd) Precautions Procedure

    furnace, and conditioned air is discharged upward. Since this CARE AND MAINTENANCE furnace can be installed in any of the 4 positions shown in Fig. 2, For continuing high performance and to minimize possible equip- you must revise your orientation to component location accord- ment failure, periodic maintenance must be performed on this ingly.
  • Page 3: Blower Motor And Wheel

    OUTER DOOR MOUNTING SCREWS VENT ELBOW RATING PLATE PRESSURE SWITCH DRAFT FLUE SAFEGUARD SWITCH COLLECTOR MAIN LIMIT SWITCH GAS MANIFOLD GAS VALVE GAS BURNER MANUAL RESET LIMIT SWITCHES FLAME SENSOR HOT SURFACE BLOWER DOOR IGNITER SAFETY SWITCH CONTROL BLOWER, MOTOR AND CAPACITOR A00342 Fig.
  • Page 4: Cleaning Heat Exchanger

    10. If a greasy residue is present on blower wheel, remove wheel 17. Turn on electrical supply. Manually close blower access door from the blower housing and wash it with an appropriate switch. Use a piece of tape to hold switch closed. Check for degreaser.
  • Page 5 A91252 Fig. 5—Cleaning Heat Exchanger Cell (5.) Repeat foregoing procedures until each cell in furnace has been cleaned. A00266 (6.) Using vacuum cleaner, remove residue from each cell. (7.) Using vacuum cleaner with soft brush attachment, clean burner assembly. (8.) Clean flame sensor with fine steel wool. (9.) Reinstall burner assembly.
  • Page 6: Electrical Controls And Wiring

    FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING NOTE 2 1-STAGE THERMOSTAT FIVE FIELD-SUPPLIED TERMINALS WIRE FUSED DISCONNECT THREE-WIRE 208/230- OR HEATING- 460-VOLT ONLY THREE PHASE 208/230- W/W1 VOLT NOTE 1 SINGLE Y/Y2 115-VOLT FIELD- JUNCTION PHASE SUPPLIED...
  • Page 8 SETUP SWITCHES TWINNING AND/OR LOW-HEAT ONLY AND COMPONENT TEST BLOWER OFF-DELAY TERMINAL ACRDJ - AIR CONDITIONING RELAY DISABLE JUMPER 24-V-THERMOSTAT TERMINALS TEST/TWIN TRANSFORMER 24-VAC CONNECTIONS 0.5-AMP024 VAC HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) PL1 - LOW VOLTAGE MAIN FUSE 3-AMP HARNESS CONNECTOR 3-AMP FUSE SEC-1...
  • Page 9: Wiring Diagrams

    SERVICE If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. LED CODE STATUS CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2. CONTINUOUS ON - Control has 24VAC power. RAPID FLASHING - Line voltage (115VAC) polarity r eversed.
  • Page 12 Copyright 2000 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 58CTS1SM Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 535-80008 Printed in U.S.A.