Carrier 100/A Series Installation, Start-Up, Operating And Service And Maintenance Instructions page 36

4-way multipoise, inducted-combustion gas furnace, input capacities: 45,000 thru 135,000 btuh
Table of Contents

Advertisement

g
START-UP,
ADJUSTMENT,
AND SAFETY
CHECK
General
FIRE HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
death and/or property
damage.
This furnace is equipped
with manual
reset limit switches
in
the gas control
area. The switches
open and shut off power
to the gas valve
if a flame rollout or overheating
condition
occurs
in
the
gas
control
area.
DO
NOT
bypass
the
switches.
Correct
inadequate
combustion
air
supply
problem
before resetting
the switches.
CUT HAZARD
Failure
to follow
this caution
may result in personal
iniury.
Sheet metal
parts may have sharp edges or burrs.
Use care
and wear
appropriate
protective
clothing,
safety glasses
and
gloves
when handling
parts and servicing
furnaces.
1. Maintain 115-v wiring and ground. Improper polarity will
result in rapid flashing LED and no furnace operation.
2. Make thermostat wire connections
at the 24-v terminal
block on the furnace control. Failure to make proper
connections will result in improper operation. (See Fig.
25 .)
3. Gas supply pressure to the furnace must be greater than
4.5-in. wc (0.16 psig ) but not exceed 14-in. wc (0.5
psig).
4. Check all manual-reset
switches for continuity.
5. Install blower compartment door. Door must be in place to
operate furnace.
6. Replace outer door.
Start-Up
Procedures
FIRE
AND EXPLOSION
HAZARD
Failure to follow this warning could cause personal injury,
death and/or property damage.
Never
test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for
the detection of leaks to check all connections.
1.
2.
3.
Purge gas lines after all connections
have been made.
Check gas lines for leaks.
To Begin Component
Self-Test:
Remove
blower
access door. Disconnect
the thermostat
R
lead from
the furnace
control
board.
Manually
close
the
blower
door switch
closed.
Short (iumper)
the COM-24v
terminal
on control
to the TEST/TWIN
3/16-inch
quick
connect
terminal
on
control
until
LED
goes
out
(approximately
2 sec). Gas valve
and humidifier
will not
be turned on. (See Fig. 24.)
ELECTRICALSHOCK
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
or death.
Blower
access door switch
opens
l15-v
power
to control.
No component
operation
can occur
unless switch
is closed.
Caution
must be taken
when
manually
closing
this switch
for service purposes.
NOTE:
The furnace
control
allows
all components,
except
the
gas valve,
to be run for short period
of time. This
feature
helps
diagnose
a system
problem
in case
of a component
failure.
Component
test feature will not operate
if any thermostat
signal is
present
at the control.
Component
test sequence
is as follows:
Refer to service label attached
to furnace or see Fig. 55.
a. LED will display
previous
status code 4 times.
b. Inducer
motor starts and continues
to run until Step f of
component
test sequence.
c. Hot surface igniter
is energized
for 15 sec., then off.
d.
Blower
motor operates
on HEAT speed for 10 sec.
e. Blower
motor operates
on COOL
speed for 10 sec.
f. Inducer
motor stops.
g. Reconnect
R lead to furnace control board, release blower
door switch and re-install
blower
door.
4. Operate
furnace
per instruction
on door.
5. Verify furnace
shut down
by lowering
thermostat
setting
below room temperature.
6. Verify furnace
restarts
by raising
thermostat
setting
above
room temperature.
Adiustments
FIRE
HAZARD
Failure
to follow
this warning
could
result
in iniury,
death
and/or property
damage.
DO NOT
bottom
out gas valve
regulator
adjusting
screw.
This can result in unregulated
manifold
pressure
and result in
excess overfire
and heat exchanger
failures.
FURNACE
DAMAGE
HAZARD
Failure
to follow
this caution
may result in reduced
furnace
life.
DO
NOT
redrill
orifices.
Improper
drilling
(burrs,
out-of-round
holes,
etc.) can cause excessive
burner
noise
and misdirection
of burner
flames.
This can result in flame
impingement
of heat exchangers,
causing
failures.
(See Fig.
53.)
Furnace
gas
input
rate
on rating
plate
is for
installations
at
altitudes
up to 2000
ft. (610
M). Furnace
input
rate must
be
within
+/-2
percent
of furnace
rating
plate input.
For altitudes
above 5500 ft. (1676
M), a field-supplied
high altitude
pressure
switch is required.
1. Determine
the correct gas input rate.
In the U.S.A.:
36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents