Carrier 100/A Series Installation, Start-Up, Operating And Service And Maintenance Instructions page 23

4-way multipoise, inducted-combustion gas furnace, input capacities: 45,000 thru 135,000 btuh
Table of Contents

Advertisement

©
A03221
Fig. 23 - Field-Supplied
Electrical
Box on Furnace
Casing
POWER
CORD
INSTALLATION
IN FURNACE
J-BOX
NOTE:
Power
cords
must
be
able to handle
the electrical
requirements
listed
in
Table
7.
Refer
to
power
cord
manufacturer's
listings.
1. Remove
cover from J-Box.
2. Route listed power cord through 7/8-in.
(22 mm) diameter
hole in J-Box.
3. Secure
power
cord to J-Box
bracket
with
a strain
relief
bushing
or a connector
approved for the type of cord used.
4. Secure field ground
wire to green ground
screw on J-Box
bracket.
5. Connect
line voltage
leads as shown
in Fig. 25.
6. Reinstall
cover
to J-Box.
Do
not pinch
wires
between
cover and bracket.
BX CABLE
INSTALLATION
IN FURNACE
J-BOX
1. Remove
cover from J-Box.
2. Route BX cable into 7/8-inch
diameter
hole in J-Box.
3. Secure
BX
cable
to
J-Box
bracket
with
connectors
approved
for the type of cable used.
4. Secure field ground
wire to green ground
screw on J-Box
bracket.
5. Connect
line voltage
leads as shown
in Fig. 25.
6. Reinstall
cover
to J-Box.
Do
not pinch
wires
between
cover and bracket.
24-V
WIRING
Make field 24-v
connections
at the 24-v
terminal
strip. (See Fig.
23.)
Connect
terminal
Y/Y2
as shown
in Fig.
24 for proper
cooling
operation.
Use only AWG No. 18, color-coded,
copper
thermostat
wire.
The
24-v
circuit
contains
an automotive-type,
3-amp..
fuse
located
on the
control.
Any
direct
shorts
during
installation,
service,
or maintenance
could
cause
this fuse to blow.
If fuse
replacement
is required,
use ONLY
a 3-amp..
fuse of identical
size.
ACCESSORIES
1. Electronic
Air Cleaner
(EAC)
Connect
an accessory
Electronic
Air
Cleaner
(if used)
using
l/4-in
female
quick
connect
terminals
to the two
male l/4-in
quick-connect
terminals
on the control board
marked
EAC-I
and EAC-2.
The terminals
are rated for
115 VAC,
1.0 amps maximum
and are energized
during
blower
motor operation.
(See Fig. 24.)
2. Humidifier
(HUM)
Connect
an
accessory
24
VAC,
0.5
amp.
maximum
humidifier
(if used)
to the
l/4-in
male
quick-connect
HUM
terminal
and
COM-24V
screw
terminal
on the
control
board
thermostat
strip.
The
HUM
terminal
is
energized
when
gas valve
relay (GVR)
is energized.
(See
Fig. 240
NOTE:
A field-supplied,
l15-v
controlled
relay connected
to
EAC terminals
may be added if humidifier
operation
is desired
during blower
operation.
NOTE:
DO
NOT
connect
furnace
control
HUM
terminal
to
HUM
(humidifier)
terminal
on Thermidistat
_ , Zone
Controller
or similar
device.
See Thermidistat,
Zone Controller,
thermostat,
or controller
manufacturer's
instructions
for proper
connection.
VENTING
The furnace
shall be connected
to a listed factory
built chimney
or vent, or a clay-tile
lined masonry
or concrete
chimney.
Venting
into
an
unlined
masonry
chimney
or concrete
chimney
is
prohibited.
When an existing
Category
I furnace
is removed
or replaced,
the
original
venting
system
may no longer be sized to properly
vent
the attached
appliances.
An improperly
sized
Category
I venting
system
could
cause
the formation
of condensate
in the furnace
and vent, leakage
of condensate
and combustion
products,
and
spillage
of combustion
products
into the living space.
il
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents