Carrier 100/A Series Installation, Start-Up, Operating And Service And Maintenance Instructions page 37

4-way multipoise, inducted-combustion gas furnace, input capacities: 45,000 thru 135,000 btuh
Table of Contents

Advertisement

The input rating foraltitudes
above 2,000 f t.(610 M)must
bereduced
by4 percent foreach 1 ,000 ft.(305 M)above
sea l evel. For i nstallations
below 2000 f t.(610 M), r efer to
the unit r ating p late. For i nstallations
above 2000 f t.(610
M),multiply t he input o nthe rating p late b ythe de-rate
multiplier inTable 8for
the correct
input rate.
In Canada:
The
input
rating
must
be
derated
by
10 percent
for
altitudes
of 2,000 ft. (610 M) to 4,500 ft. (1372
M) above
sea level
by
an authorized
Gas
Conversion
Station
or
Dealer.
To determine
correct
input
rate for altitude,
see
example
1 and use 0.90 as derate multiplier
factor.
EXAMPLE
1:
88,000 BTUH INPUT FURNACE INSTALLED AT 4300
FT.(1310M)
Furnace
Input
X
Derate
=
Furnace
Input
Rate at Sea
Multiplier
Rate at
Level
Factor
Installation
Altitude
88,000
X
0.90
=
79,200
2. Determine
the
correct
orifice
and
manifold
pressure
adjustment.
There
are two different
orifice
and manifold
adjustment
tables. All models
in all positions,
except Low
NOx
models
in downflow
or horizontal
positions,
use
Table 13 (22,000
Btuh/Burner).
Low NOx models
in the downflow
or horizontal
positions
must use Table 14 (21,000
Btuh/Burner).
See input
listed
on rating
plate.
a. Obtain average yearly gas heat value (at installed altitude)
from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation
altitude
in Table 13 or 14.
d. Find closest
natural
gas heat value and specific
gravity
in Table 13 or 14.
e. Follow
heat value and specific gravity
lines to point of
intersection
to find orifice
size and manifold
pressure
settings
for proper operation.
f. Check and verify burner
orifice size in furnace.
NEVER
ASSUME
ORIFICE
SIZE.
ALWAYS
CHECK
AND
VERIFY.
g. Replace
orifice with correct
size if required
by Table 10,
12, 13, and 14. Use only factory-supplied
orifices.
See
EXAMPLE
2.
Caution!!
For the following
applications,
use the minimum
vertical
vent heights
as specified
below.
For all other
applications,
follow exclusively
the National
Fuel Gas Code.
FURNACE
FURNACE
INPUT
VENT
ORIENTATION
ORIENTATION
(BTUH/HR)
Downflow
Vent elbow
left, then
up Fig. 38
132,000
Horizontal
Left
Vent elbow
right, then
up Fig. 41
132,000
Horizontal
Left
Vent elbow
right
Fig. 42
132,000
NOTE: All vent configurations
must also meet National Fuel Gas Code venting requirements
NFGC
*4 in. (102 mm) inside casing or vent guard
**Including
4 in. (102 mm) vent section(s)
MIN. VENT
MIN. VERTICAL VENT
DIAMETER
HEIGHT
IN (MM)*
FT. (M)**
5 (127 )
12 (4)
5 (127 )
7 (2)
5 (127 )
7 (2)
Table
10 - Altitude
Derate Multiplier
for U.S.A.
ALTITUDE
PERCENT
DERATE
(FT. / M)
OF
MULTIPLIER
DERATE
FACTOR*
0-2000
(0-610)
0
1.00
2001-3000
(610-914)
8-12
0.90
3001-4000
(914-1219)
12-16
0.86
4001-5000
(1219-1524)
16-20
0.82
5001-6000
(1524-1829)
20-24
0.78
6001-7000
(1829-2134)
24-28
0.74
7001-8000
(2134-2438)
28-32
0.70
8001-9000
(2438-2743)
32-36
0.66
9001-10,000
(2743-3048)
36-40
0.62
* Derate multiplier factors are based on midpoint altitude for altitude
range.
3. Adjust manifold
pressure
to obtain correct
input rate.
a. Turn gas valve ON/OFF
switch to OFF.
b. Remove
manifold
pressure
tap plug from gas valve. (See
Fig. 52.)
c. Connect
a water column
manometer
or similar
device to
manifold
pressure
tap.
d. Turn gas valve ON/OFF
switch to ON.
e. Manually
close blower
door switch.
f. Set thermostat
to call for heat.
g. Remove
regulator
seal cap and turn regulator
adjusting
screw counterclockwise
(out) to decrease
input
rate of
clockwise
(in) to increase
input rate.
EXAMPLE
2:(0
to 2000 ft. (0 to 610 M) altitude)
For 22,000
Btuh per burner
application
use Table 13.
Heating
value = 1000 Btuh/cu
ft.
Specific
gravity = 0.62
Therefore:
Orifice No. 43"
Manifold
pressure:
3.7-in.
wc
*Furnace
is shipped
with No. 43 orifices.
In this example
all main burner
orifices are the correct
size and do not need to be changed
to obtain
proper
input rate.
h. Install regulator
seal cap.
i. Leave
manometer
or similar
device
connected
and
proceed
to Step 4.
NOTE:
DO NOT
set manifold
pressure
less than 3.2-in
wc or
more
than
3.8-in.
wc for natural
gas at sea level.
If manifold
pressure
is outside
this range, change
main burner
orifices.
Refer
to Table 10, 12, 13, and 14.
NOTE:
If orifice hole appears
damaged
or it is suspected
to have
been
redrilled,
check
orifice
hole with
a numbered
drill bit of
correct
size.
Never
redrill
an orifice.
A burr-free
and squarely
aligned
orifice
hole is essential
for proper flame characteristics.
4. Verify natural
gas input rate by clocking
meter.
NOTE:
Gas valve regulator
adjustment
cap must be in place for
proper input to be clocked.
a. Turn off all other gas appliances
and pilots served by the
meter.
b. Run furnace
for 3 minutes
in heating
operation.
il
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents