Miele PDR 908 EL Operating And Installation Instructions page 87

Vented
Hide thumbs Also See for PDR 908 EL:
Table of Contents

Advertisement

External applications
External exhaust flap
External hardware is connected via the
Miele XCI Box.
The time delay between the external
exhaust-air flap's activation point and
the switch-on time for the drum/fan
motor is regulated.
A message appears in the display while
the exhaust-air flap is open.
– Factory default: Off
This option must always be selected
if there is no exhaust-air flap to
activate. This prevents the program
from being canceled.
– On
– 0 seconds
– 1 second
– 2 seconds
 ...
– 300 seconds
Supervisor level
Additional fan
External hardware is connected via the
Miele XCI Box.
If an extra fan is connected, it must be
switched on at the same time as the
drive unit.
– Off
– On
Pressure sensor
External hardware is connected via the
Miele XCI Box.
When using a shared exhaust-air duct,
one tumble dryer may have to be
switched off or suppressed from the
outset if certain pressure levels have
built up in the ducting. Because the
pressure sensor is an external unit,
there is the option of reading in both a
logical normally open contact or a
normally closed contact.
A message appears in the display while
the exhaust-air flap is open.
– Off = Not active
– NO contact = Active
Responds to high potential
– NC contact = Active
Responds to low potential
87