5 – Wiring
continued

5-3 Electrical and Cable Data

AC Input and Output (75°C Minimum Copper Wire)
Maximum Current
54.3 amperes

5-4 AC Input/Output Wiring Instructions

1
Use M3 pan-head screws
S5
2
Route the AC input/output wiring through cable sleeves and route the cable sleeves through the knockouts in the terminal block cover
Each input/output wire should terminate with a ring terminal.
3
Connect the ring terminal for each input/output cable to the appropriate input/output terminals. Tighten the terminals with at least 2.60 N•m
of torque.
4
Secure the input/output cable bundles to the cable attachment tray with the included mounting ties
5
Use M3 pan-head screws
S5
A1
1
3
A3
4
Conductor Diameter
4.6 mm (#6 AWG)
to attach the cable attachment tray
to secure the terminal block cover
S5
A3
Torque Force
2.60 N•m (23 in•lb)
beneath the terminal block.