Ups Installation For Parallel Systems; Input And Output Wiring - Tripp Lite S3M100KX Owner's Manual

Smartonline s3m series 3-phase ups systems input: 220/230/240v (ph-n), 380/400/415v (ph-ph), 3o 4-wire + pe
Hide thumbs Also See for S3M100KX:
Table of Contents

Advertisement

3. Installation and Setup

3.6 UPS Installation for Parallel Systems

Warning:
• The input harmonic current distortion will be between 3% and 4.5% in parallel UPS operations.
• One parallel kit is needed for every two UPS systems.

3.6.1 Input and Output Wiring

1. When installing the parallel system, the length of input wires (R, S, T, N) in one UPS must be equal to the input wires of the other UPS.
Likewise, the length of output wires (R, S, T, N) must also be in equal length. If not, it will cause unbalance current on the output load.