Cooling system manufacturers
ait-deutschland GmbH
BKW Kälte-Wärme-Versorgungstechnik GmbH
DELTATHERM Hirmer GmbH
Glen Dimplex Deutschland GmbH
Helmut Schimpke und Team Industriekühlanlagen
GmbH + Co. KG
Hydac System GmbH
Hyfra Industriekühlanlagen GmbH
Pfannenberg GmbH
Note
Other manufacturers
You can also use equivalent products from other manufacturers.
Responsibility for the properties of third-party products resides with the plant
manufacturer.
4.1.3.3

Engineering the cooling circuit

Note
Observing the maximum permitted pressure
The maximum permitted pressure in the cooling circuit is 0.7 MPa (7 bar).
If a pump is deployed that produces a higher pressure, the produced pressure must be
limited by the plant with suitable measures (safety valve p ≤ 0.7 MPa, pressure control)
to the maximum permitted pressure.
● Specify the working pressure depending on the flow conditions in the supply and
return of the cooling circuit.
Select the smallest possible pressure difference between the supply and return so
that pumps with a flat characteristic curve can be used.
● Set the required coolant flow rate per time unit according to the technical data of the
equipment and motors.
Note
Install a backflush filter in the cooling circuit to prevent blockage and corrosion so that
any deposited material is flushed out.
SIMOTICS M-1FE1 synchronous built-in motors
Configuration Manual, 09/2019, A5E47872980B AA
Motor components, characteristics and options
www.kkt-chillers.com
www.bkw-kuema.de
www.deltatherm.de
www.riedel-cooling.com
www.schimpke.org
www.hydac.com
www.hyfra.de
www.pfannenberg.com