11. Long-Term Storage

WARNING : INJURY
 Always turn the starter switch to the STOP position and stop the engine, then close
and lock OPERATION PANEL DOOR before checking or maintaining the engine or
any equipment.
CAUTION : FIRE
 Always be sure to wipe up any spilled fuel or oil.
 Allow the generator to cool before covering with the protective cover.
CAUTION : BURNS
 Do not touch the engine and surrounding components immediately after stopping the
engine as they are still extremely hot.
(1) Storage Procedures
Perform the following maintenance procedures before storing this generator if it is not going to
be used for two months or more.
Remove the battery. (Refer to section "8-8. Checking the Battery".)
1
2
Replace the engine oil.
(Refer to section "10. Inspection/Maintenance (1) Engine Oil Replacement".)
3
Drain the fuel from the fuel tank and filter.
(Refer to section "10. Inspection/Maintenance (5) Draining Water from the Fuel Filter
(Pre Filter)".)
(Refer to section "10. Inspection/Maintenance (11) Draining Water from the Fuel
Tank".)
4
Drain the DEF from the DEF tank.
5
Clean up and inspect inside of the spill containment.
(Refer to section "10. Inspection/Maintenance (15) Flushing Liquid in Spill
Containment".)
6
Store in a secured location.
7
Clean up all generator components, and store in a dry and dust-free location. Also cover
when storing so that rain cannot enter through the suction or exhaust ports.
< Note >
 Adjust the fluid of the removed battery to the appropriate level and recharge approximately
every month.