(Ex.) If used voltage is 208 V and voltage drops by 10.4 V.
Length 100 ft (30 m)
or less
Current
50 A
10
100 A
6
150 A
6
200 A
4
250 A
2
300 A
2
(Ex.) If used voltage is 120 V and voltage drops by 6 V.
Length
Current
10 A
20 A
30 A
50 A
100 A
150 A
200 A
250 A
300 A
350 A
400 A
450 A
500 A
Three-phase: Cabtyre cables
200 ft
300 ft
(61 m)
(91 m)
6
4
2
1
1/0
1/0
Single-phase Cabtyre cables
100 ft. (30 m)
200 ft. (61 m)
or less
14
10
8
6
4
2
1
1/0
2/0
2/0
3/0
3/0
4/0
400 ft
(122 m)
6
4
2
1
1
1/0
1/0
3/0
2/0
4/0
3/0
4/0
300 ft. (91 m)
10
8
8
6
6
4
4
2
1
2/0
2/0
4/0
3/0
4/0
25
(Unit: AWG)
500 ft
600 ft
(152 m)
(183 m)
2
2
1/0
1/0
2/0
3/0
4/0
4/0
(Unit: AWG)
400 ft. (122 m)
8
4
2
1
3/0