Shindaiwa DGK180F Owner's And Operator's Manual page 23

Diesel engine generator
Table of Contents

Advertisement

* Check that 208 V is displayed during operation if using at the three-phase 208 V setting.
Check that 480 V is displayed during operation if using at the three-phase 480 V setting. The
voltage of single-phase three-wire output of "U-W Voltage" is a value that is one half of the
displayed voltage meter value.
(2) Ammeter
Displays the output current (phase current) of the generator. Turn the ammeter selector switch
to "L1+U" to display the output current of the three-phase L1 phase and single-phase U phase.
Turn the switch to "L3+W" to display the output current of the three-phase L3 phase and
single-phase W phase. "L2" displays the output current of three-phase output terminal L2.
< Note >
 If measuring the output current for a single-phase three-wire type, turn the ammeter selector
switch to "L1+U" or "L3+W". The voltage cannot be accurately measured if set to "L2".
(3) Frequency Meter
Displays the frequency of the power source. Check that 60 Hz is displayed during operation.
Indicators
(1) Glow Lamp
This lamp illuminates when the starter switch is on START
positon. This lamp turns off when pre-heating is completed.
This lamp turns off and the generator starts.
< Note >
 Pre-heating time depends on the coolant temperature, and
should be completed in approximately 0 to 16 sec.
(2) Pilot Lamp
This lamp illuminates when the engine is operating to indicate
that power is being generated.
Switches
(1) Starter Switch
The engine warms up and starts automatically.
 START
The engine is started in this position.
The engine warms up and starts automatically.
 STOP
The engine is stopped, and the power supply
is turned off completely in this position. You
can operate the ACCESSORY switch in this
position.
 AUTO
The engine is started in this position when the
REMOTE START terminal closes.
(2) Accessory Switch
If you select ON, the display turns on, activate the
electromagnetic pump, you can check the fuel
level and you can bleed air from the fuel system.
Accessory Switch
Remote Start Terminal
20
Pilot Lamp
Glow Lamp
3-Phase
1-Phase
Breaker
Breaker
Breaker Trip
Selector Switch
Ammeter
Selector Switch
Starter Switch

Hide quick links: