(2) Oil Pressure / Water Temp / Speed Monitor
Displays the engine speed, water temperature and oil pressure. Switching the selector switch
changes the display in the following order: Speed  Water temp  Oil press. Engine speed is
displayed first when the engine is started.
 Speed
Displays the engine speed. 1800rpm is displayed at 60 Hz.
 Water Temp
Displays the temperature of the engine coolant. Normal
temperature displayed during operation should generally
between 167°F (75℃) and 194°F (90℃) depending on
usage.
< Note >
 If the coolant temperature rises above 212 °F(100℃), immediately stop all connected
equipment to the generator, and idle the engine while cool down the coolant temperature.
 Oil Press
Displays the pressure of the engine lubrication system. Normal pressure displayed during
operation should generally between 42 and 71 psi (2.90 – 4.90 x 100 kPa) depending on
usage. However, the pressure may rise above this range just after starting a cold engine. Idle
the engine until it reaches the normal pressure.
(3) Fuel Level
It shows the amount of fuel in the tank.
All lamps are lit when the amount reaches to the maximum level, and FULL is lit.
The lit lamp decreases as the amount of fuel in the tank reaches to EMPTY.
The fuel level on the control panel will only display the fuel level for the internal fuel tank.
(4) Fuel Leak Warning Indicator
Fuel Leak Warning Indicator illuminates if the Fuel stored in the fuel tank leaked. If it illuminates,
immediately stop the engine please contact distributor or dealer for repair.
< Note >
When the fuel leak warning Indicator illuminates during operation, stop the engine, check for
fuel, oil, cooling water and DEF leakage, and repair as necessary.
Do not use the equipment with liquid accumulated in the spill containment. Drain the spill
containment before operation.
Generator Meters and Gauges
(1) Voltmeter
The voltmeter displays the three-phase output
voltage (voltage between L1-L3). Check that 240
V is displayed during operation. Output voltage for
single-phase three-wire (voltage between U-W) is
the same voltage as the three-phase output
voltage (voltage between L1-L3). Accordingly, use
the voltage meter displayed value as a reference.
19
Oil Press
Water Temp
Speed
Fuel Level
Fuel Leak
Warning
Selector
Switch