 Power available for use by each output terminal and receptacle are as show below.
CON1
Load
CON2
Load
 Use is possible up to the kVA as shown below.
1-phase, 3-wire
output terminal
U-W
108/ [54]*
U-N
54/ [27]*
W-N
54/ [27]*
* Figures in brackets are used when set to 480 V.
< Note >
 If using a single-phase 120 V (between output terminals U-N and W-N), connect an
equivalent load between U-N and W-N.
 If using a single-phase three-wire output terminal simultaneously with a receptacle output,
make sure that currents passing through each phase is less than the rated current of this
generator.
 If using at the three-phase 480 V setting, the output voltage of the single-phase three-wire
type is single-phase 240/120 V, which is the same as the three-phase 208/240 V setting.
Accordingly, care must be taken to not draw an excessive load as the available power is only
one half.
N
U
GROUND
U-N / W-N / U-W
U-N
W-N
CON3
CON5
Load
CON4
Load
1-phase 120 V receptacle
CON1
CON2
CON3
Total 2.4
W
CON5,CON6,CON7
120V
(W-N)
CON6
CON7
Load
Load
Load
1-phase 240/120 V
receptacle
CON4
CON5
Total 2.4
12
28
120V
(U-N)
W
X
240V
(U-W)
Y
(Unit: kVA)
Total
CON6
CON7
108/ [54]*
12
12
54/ [27]*
54/ [27]*