Connection Drawing Of Pipeline System; Water Quality; Water Quality Control; Applicable Standard Of Water Quality For The Unit - Midea Aqua Tempo Super Series Technical & Service Manual

Air-cooled scroll chiller, 3 phase, 380-415v, 50hz
Hide thumbs Also See for Aqua Tempo Super Series:
Table of Contents

Advertisement

Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)

13.2.2 Connection drawing of pipeline system

unit
unit

13.2.3 Water quality

※Water quality control

When industrial water is used as chilled water, little furring may occur; however, well water or river water,
used as chilled water, may cause much sediment, such as furring, sand, and so on. Therefore, well water or
river water must be filtered and softened in softening water equipment before flowing into chilled water
system. If sand and clay settle in the evaporator, circulation of chilled water may be blocked, and thus
leading to freezing accidents; if hardness of chilled water is too high, furring may occur easily, and the
devices may be corroded. Therefore, the quality of chilled water should be analyzed before being used, such
as PH value, conductivity, concentration of chloride ion, concentration of sulfide ion, and so on.

Applicable standard of water quality for the unit

PH
Total
Conductivity
value
hardness
<20μV/cm(25℃)
<50ppm
7~
8.5
25/35/65/80/130kW module
Differential pressure by-pass valve
Auxiliary electric heater
Sulfide
Chloride
Ammonia
ion
ion
ion
No
<50ppm
No
93
Expansion tank
Water replenishing
Dirt discharge valve
Drain valve
Sulfate
Silicon
ion
<50ppm
<30ppm
MCAC-ATSM-201606
Terminal
Two-way valve
Three-way valve
Iron
Sodium ion
content
<0.3ppm
No
requirement
Calcium
ion
<50ppm