MCAC-ATSM-201606
12) The unit inlet water temperature sensor malfunction
The unit inlet water temperature
sensor malfunction
The unit's circuit of inlet water
temperature sensor is broken.
The unit's circuit of inlet water
temperature sensor is shorten.
The unit's joint of inlet water
temperature sensor is loose.
PCB mistakes to alarm.
Inform
the
center.
13) Pipe temp. sensor of condenser malfunction
Pipe
temperature
condenser malfunction.
The circuit of condenser's pipe
temperature sensor is broken.
The circuit of condenser's pipe
temperature sensor is shorten.
The joint of condenser's pipe
temperature sensor is loose.
PCB mistakes to alarm.
Inform
the
center.
Yes
Yes
No
Yes
No
Yes
No
Yes
No
customer
service
sensor
of
Yes
Yes
No
Yes
No
Yes
No
Yes
No
customer
service
Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
Replace temperature sensor.
Replace temperature sensor.
Fixed joint.
Replace PCB.
Replace temperature sensor.
Replace temperature sensor.
Fixed joint.
Replace PCB.