Current Protection; High Temperature Protection Of Condenser - Midea Aqua Tempo Super Series Technical & Service Manual

Air-cooled scroll chiller, 3 phase, 380-415v, 50hz
Hide thumbs Also See for Aqua Tempo Super Series:
Table of Contents

Advertisement

Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)

2) Current protection

Current protection
The fin of heat exchanger is
dirty or aged in cooling mode,
or
the
strong.
The fan motor stopped running
in cooling mode, reversal and
run slowly. The water pump
didn't start up or less water
flow in heating.
Air is in system, filled too much
refrigerant(Generally happened
after maintenance.)
Abnormal power supply.
PCB mistakes to alarm.
Inform the customer service
center.

3) High temperature protection of condenser

High temperature protection of
condenser.
The fin of heat exchanger is
dirty or aged in cooling mode.
The installation position of unit
results in bad heat transfer of
condenser.
In cooling mode, the fan motor
stop running, reversal and run
slowly.
The temperature sensor of
condenser bring drifting when
collect temperature.
PCB mistakes to alarm.
Inform the customer service
center.
Yes
Yes
shell-tube
scaled
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
No
No
No
No
Clean heat exchanger.
Check the fan motor,
capacitor (1 phase) or
start up water pump.
Empty, vacuuming and
append
refrigerant
necessary.
Check
power
supply,
start up the unit after
normal power supply.
Replace PCB.
Yes
Clean heat exchanger.
Yes
Replace
installation
position of unit.
Check the fan motor,
Yes
capacitor (1 phase).
Replace
temperature
Yes
sensor.
Yes
Replace PCB.
81
MCAC-ATSM-201606