Error Alarm Handling; Installation Procedure - Midea Aqua Tempo Super Series Technical & Service Manual

Air-cooled scroll chiller, 3 phase, 380-415v, 50hz
Hide thumbs Also See for Aqua Tempo Super Series:
Table of Contents

Advertisement

MCAC-ATSM-201606
3) Press the "▲" or "▼" key to adjust the main unit serial number can query 16 sets main units status
information from #0~#15. Press " " or " " to adjust the spot check sequence number of one main unit
then can query all the status information of this unit. Spot check content according to the main unit model
wired controller:
1
outlet water temperature Tou->2、inlet water temperature Tin->
3
outdoor ambient temperatures T4->4、outdoor pipe temperatureT3A->
5
outdoor pipe temperatureT3B->6、current of the compressor IA->
7
current of the compressorIb->8、anti-frozen temperature T6->
electronic expansion valv opening FA->10、electronic expansion valv opening Fb->
9
11
Last one error or protection
13
Last third error or protection

16.2.5. Error alarm handling

When the unit has error or protection, "
enter spot check, and then press the "▲" or "▼" key to query the unit of 0-15#, if the error icon was on
during query, that means the corresponding outdoor unit has error or protection at that time, and then can
spot check the last 1, 2, 3 times error or protection of this outdoor unit. After clear the error or protection, the
error icon will disappear.

16.2.6. Installation procedure

->12、
Last second error or protection
->1、
outlet water temperature Tou
" icon will be flashed. Long press "Setting" for 3 seconds to
Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
->
......
128