Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
7) Power supply phase sequence malfunction
Power supply phase sequence
malfunction.
Phase sequence error.
Lack of phase.
Phase lack protector is broken.
PCB mistakes to alarm.
Inform the customer service
center.
8) Communication malfunction
Communication malfunction
No power input to unit or wired
controller.
Communicating wire malfunction.
Address repeat.
PCB mistakes to alarm.
The attachments of unit have
strong
interference.
Inform the customer service
center.
Yes
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
No
Yes
No
Yes
No
Yes
No
Yes
electromagnetic
No
Adjust connecting wire.
Check power supply.
Replace
phase
lack
protector.
Replace PCB.
Inspect power supply.
Inspect
communicating
wire.
Adjust address.
Replace PCB.
Reduce electromagnetic
interference.
83