Low Pressure Protection - Midea Aqua Tempo Super Series Technical & Service Manual

Air-cooled scroll chiller, 3 phase, 380-415v, 50hz
Hide thumbs Also See for Aqua Tempo Super Series:
Table of Contents

Advertisement

MCAC-ATSM-201606
Discharge
protection.
Discharge
switch is broken or joint
is loose.
Refrigerant is too less.
Couldn't open the EXV.
The EXV, capillary and filter
are dirty, blocked and ice
blocked.
PCB mistakes to alarm.
Inform
service center.

2) Low pressure protection

Low pressure protection.
Refrigerant is too less.
Couldn't open the EXV.
The EXV, capillary and filter are
dirty, blocked and ice blocked.
The
pressure
broken or joint is loose.
Anti-freezing
protection.
Inform the customer service
center.
temperature
Yes
temperature
Yes
No
Yes
No
Yes
No
No
Yes
No
Yes
No
the
customer
Yes
Yes
No
Yes
No
Yes
No
Yes
controller
is
No
Yes
lower
pressure
No
Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
Replace
discharge
temperature switch, fixed
joint.
Detect leakage for all
system,
append
refrigerant.
Replace the EXV or coil.
Cause
of
dirty
and
blocked,
replace
the
EXV, capillary and filter.
Vacuuming and append
refrigerant if ice blocked.
Check
if
happened
frequently, if yes, please
replace PCB.
Inspect
leakage
in
system,
append refrigerant.
Replace the EXV and coil.
Cause of dirty and blocked,
replace the EXV, capillary and
filter. Vacuuming and append
refrigerant if ice blocked.
Replace the pressure controller,
fixed joint.
Inspect if the water flow is
normal, refer to the water flow
malfunction to analysis.
80