80Kw Module Pcb, Outlook View; 80Kw Module Components Description - Midea Aqua Tempo Super Series Technical & Service Manual

Air-cooled scroll chiller, 3 phase, 380-415v, 50hz
Hide thumbs Also See for Aqua Tempo Super Series:
Table of Contents

Advertisement

Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)

16.1.3 80kW module PCB, outlook view

34
35
33
9
12
7
17
18
15
16
32

16.1.4 80kW module components description

No.
Detail information.
1
Detection of current of compressor A1 (Protection code P4).
Detection of current of compressor B1 (Protection code P5).
2
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the compressor is
detected to exceed protective value set (33A for constant speed compressor), it will be shut down and re-started after 3 min.
T4: outdoor ambient temperature sensor (Fault code E7).
T3B: pipe temperature sensor of condenser B (Fault code E6 and protection code P7).
T3A: pipe temperature sensor of condenser A (Fault code E5 and protection code P6).
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit. Start
outdoor fan A only, start A and B gears, and control the unit through T4.
2) T3B and T3A: when the electric control of the scroll unit detects the temperature of the outdoor pipe T3A or T3B of the
3
system exceeds the protective temperature 65℃, the corresponding system will be shut down. And it will be re-started up,
after the temperature drops below the recovery temperature 60℃. Another system will be not affected.
3) T4, T3B and T3A: when the temperature sensor is detected to suffer open circuit or short circuit, fault alarm will occur.
● When the main unit suffer fault of temperature sensor: the main unit and subordinate units will be shut down.
● When the subordinate unit suffer fault of temperature sensor: the unit will be shut down, but other subordinate units will
not be affected.
4
Detection of current of the compressor A2 (Protection code P4)
5
Unit outlet water temperature sensor (Fault code E4).
10 11
6
5
14
13
19
20
31
3
22
4
37
30
29
21
23
36
113
MCAC-ATSM-201606
26
27
1
2
8
28
24
25
38