13.Installation

13.1 Unit Installation

13.1.1 Transportation

The angle of inclination should not be more than 15º when carrying the unit, to avoid overturn of the unit.
a. Rolling handling: several rolling rods of the same size are placed under the base of the unit, and the
length of each rod must be more than the outer frame of the base and suitable for balancing of the unit.
b. Lifting: the strength lifting rope (belt) can bear should be 4 times the weight of the unit. Check the lifting
hook and ensure that it is firmly attached to the unit, and the lifting angle should be more than 60º . To avoid
damages to the unit, the contact position of the unit and lifting rope should be provided with an at least
50mm thick wood block, cloth or hard paper. Any person is not allowed to stand below the unit when lifting it.
Hoisting rope

13.1.2 Installation space

● Requirements of arrangement space of the unit
1) To ensure adequate airflow entering the condenser, the influence of descending airflow caused by the
high-rise buildings around upon the unit should be taken into account when installing the unit.
2) If the unit is installed where the flowing speed of air is high, such as on the exposed roof, the measures
including sunk fence and Persian blinds can be taken, to prevent the turbulent flow from disturbing the air
entering the unit. If the unit needs to be provided with sunk fence, the height of the latter should not be more
than that of the former; if Persian blinds are required, the total loss of static pressure should be less than the
static pressure outside the fan. The space between the unit and sunk fence or Persian blinds should also
meet the requirement of the minimum installation space of the unit.
3) If the unit needs to operate in winter, and the installation site may be covered by snow, the unit should be
located higher than the snow surface, to ensure that air flows through the coils smoothly.
Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
25/35/65/80/130kW module
Lifting hole
88
Lifting equipment
The position should be provided with an at
least 50mm thick wood block, cloth or hard
paper, to avoid damages to the unit.
Lifting hole