Wiring Of “On/Off” Weak Electric Port; Remote Mode Selection; Wiring Of “Alarm” Port - Midea Aqua Tempo Super Series Technical & Service Manual

Air-cooled scroll chiller, 3 phase, 380-415v, 50hz
Hide thumbs Also See for Aqua Tempo Super Series:
Table of Contents

Advertisement

Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
1 .Wiring of "ON/OFF" weak electric port
Corresponding parallel connect the "ON/OFF"(dry contact input signal) port of the main unit's electric control
box, then, connect the "ON/OFF" signal (provide by user) to the "ON/OFF" port of main unit as follows.
2 .Remote mode selection: Wiring of "HEAT/COOL" weak electric port
Corresponding parallel connect the "HEAT/COOL" (dry contact input signal) port of the main unit's electric
control box, then, connect the "ON/OFF" signal (provide by user) to the "HEAT/COOL" port of main unit as
follows.
3 .Wiring of "ALARM" port
Connect the device provided by user to the "ALARM" (dry contact output signal) ports of the module units as
follows.
If the unit is operating normally, the ALARM port is closed, otherwise, the ALARM port is not closed.
0# electric
control box
"ON/OFF" port
Red
Blue
0# electric
control box
"HE AT/COOL" por t
Brown
Black
electric control box
"ALARM" port
Red
Red
105