10. Error messages and rectification
Fault / error message
System does not respond
Door travels to the CLOSE end position when
the OPEN button is pressed
Door travels to the OPEN end position when
the CLOSE button is pressed
ERROR END POSITION
ERROR RUN TIME
ERROR SEP
ERROR PRESSURE SENSOR TESTING
ERROR ROT. FIELD
ERROR RS 485
ERROR POWER
After rectifying the cause of the fault, the controls must be disconnected briefly from the mains!
 – CS 300 Gate Controls / Rev. 5.3
Cause
- No voltage supply
- Rotating field is connected wrongly
- The door has travelled beyond one of the end
positions
- The end positions have not been programmed
yet
- The programmed running time has been
exceeded
- The safety edge protection is faulty
- Safety edge protection was triggered
- The PS switch is not activated at the CLOSE
end position
- An incorrect rotating field is connected to
terminal X1
- Communications fault between the end
position switch and the controls
- The power monitoring has been triggered
Rectification
- Check the voltage supply of the drive and the
controls
- Check the rotating field and establish clock-
wise rotating field if necessary
- Check the programming of the end positions
and reset them if necessary
- Check the path of the door
- Re-programme the running time
- Check the safety edge protection and the
spiral cable
- Remove obstruction from path of door
- Check the PS switch, spiral cable and profile
- Check the setting for the CLOSE end position
- Ensure that a clockwise rotating field is
connected
- Check the cable and socket connections
- Check that the door can move freely
- Reset the power value